| 2005-01-26 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- PROVIDE COMPLETE BATHROOM WITH A DOOR |
| | THAT ALLOWS 29" MIN. CLEAR OPENING. SEC. |
| | 11-11 FBC 2001. |
| | |
| | 2- SPECIFY ROOF TILE FASTENING. SECTION |
| | 104.2.1.1 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 3- UPDATE TRUSS ANCHOR SCHEDULE. PROVIDE |
| | COMPLETE ENGINEERING CALCULATIONS FOR |
| | TYPE & NUMBER OF FASTENERS THAT DIFFER |
| | FROM THOSE TESTED AND PUBLISHED BY THE |
| | MANUFACTURER TO COMPLY WITH SECTION |
| | 1609.4.3 FBC 2001. |
| | |
| | 4- A)TITLE BLOCK NEEDS NAME OF ARCHITECT |
| | SEALING PLANS. CHAPTER 61G1-16004 FAC. |
| | B) STATE REGISTRATION NUMBER IS |
| | INCORRECT. REVISE AS REQUIRED. |
| | |
| | 5- PROVIDE DETAIL/SPECS FOR INSTALLATION |
| | OF CEILING AT ENTRY AND REAR PORCHES. |
| | SPECIFY FASTENERS AND SPACING. SEE ASTM |
| | C926 AND ASTM C1063. SEC. 2504.2 FBC. |
| | |
| | 6- ENERGY CALCULATIONS: OWNER/AGENT TO |
| | SIGN AND DATE FORM. |
| | |
| | 7-PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR: A) ENTRY DOORS. |
| | B) FRENCH DOORS. SEE SIZES ON PLANS. |
| | C) CONCRETE LINTELS: NEED DADE COUNTY |
| | NOA THAT MATCHES ONE SUBMITTED FOR |
| | FLORIDA PRODUCT APPROVAL. |
| | D) FIXED WINDOWS THAT MEET THE DESIGN |
| | PRESSURES CALCULATED ON PLANS. SEE PLANS |
| | FOR SIZES AND DESIGN PRESSURES. |
| | E) ARABESQUE WINDOW AS SHOWN ON PLANS. |
| | |
| | 8- A) PROVIDE COMPLETE UL LISTING AND |
| | SPECS FOR FIREPLACE. SEC. 2806 FBC. |
| | B) PROVIDE COMPLETE APPROVED BBQ SPECS. |
| | SEC. 2808 FBC 2001. |
| | |
| | 9- STORM SHUTTERS: A) KEY PLAN DOESN'T |
| | MATCH PLANS. |
| | B) REVISE MINIMUM PANEL SIZE. SEE |
| | ENGINEERED DRAWINGS FOR LIMITATIONS. |
| | C) REVISE INTERIOR AND END ZONES. SEE |
| | PLANS FOR LOCATION. |
| | D) REVISE DESIGN PRESSURES. SEE PLANS. |
| | |
| | 10- PROVIDE COMPLETE FRAMING DETAILS FOR |
| | ARABESQUE WINDOW. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 11- OWES $866.23 FOR UPDATED VALUATION. |
| | |
| | 12- REVISE FOUNDATION NOTE #2 ON SHEET |
| | A-2. SEE CHAPTER 19 FBC 2001 FOR PROPER |
| | ACI REFERENCE. |
| | |
| | 13- REVISE DETAIL CONNECTORS SHOWN ON |
| | DETAIL 2/A-9. "SEMCO" IS OUT OF |
| | BUSINESS. |
| | |