| 2005-06-06 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | |
| | 1- NOTE ON DRAWING A-3 CALLS FOR IMPACT |
| | GLAZING IN DOORS AND WINDOWS. SHUTTERS |
| | INSTALLATION SCHEDULE SHOWSMISSILE |
| | IMPACT GLAZING IN DOORS AND WINDOWS. |
| | PRODUCT APPROVALS SUBMITTED FOR DOORS |
| | AND WINDOWS ARE FOR NON IMPACT GLAZING. |
| | NEED TO CLARIFY WHICH METHOD OF GLASS |
| | PROTECTION IS GOING TO BE USED AND |
| | PROVIDE COMPLETE INFORMATION FOR EITHER |
| | METHOD. |
| | |
| | 2- FRONT ELEVATION TO SHOW EXACT TYPE OF |
| | ENTRY DOORS FOR WHICH PRODUCT APPROVAL |
| | WILL BE SUBMITTED. |
| | |
| | |
| | 3- REVISED ENERGY CALCULATIONS WERE |
| | REQUIRED BECAUSE A/C AREA WAS INCREASED. |
| | REVISED ENERGY CALCULATIONS WERE NOT |
| | SUBMITTED. |
| | |
| | 4- TRUSS ANCHOR SCHEDULE: REVISE |
| | CONNECTOR THD210 AND THD210-2. THIS IS A |
| | WOOD TO WOOD CONNECTOR. NEED A MASONRY |
| | TO WOOD CONNECTOR. SEE CATALOGUE FOR |
| | PROPER MASONRY CONNECTOR. |
| | |
| | 5- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR: A) FRENCH DOORS THAT MATCH |
| | SIZE OF DOORS SHOWN ON PLANS. PRODUCT |
| | APPROVAL SUBMITTED IS FOR 6'-8" HIGH |
| | DOORS. NEED 8'-0" HIGH DOORS. |
| | |
| | B) CASEMENT WINDOWS: DADE COUNTY NOA |
| | REPORT DOESN'T MATCH REPORT SUBMITTED |
| | FOR FLORIDA PRODUCT APPROVAL. RESUBMIT |
| | CORRECT DADE COUNTY NOA REPORT. |
| | |
| | 6- SPECIFICATIONS FOR BBQ WERE FORWARDED |
| | TO BUILDING OFFICIAL FOR APPROVAL. BLDG |
| | OFFICIAL IS OUT THIS WEEK. |
| | NOTE: THERE ARE COMPANIES WHO HAVE |
| | DESIGNED BBQ TO BE SPECIFICALLY |
| | INSTALLED IN PORCHES OR LANAIS AND THE |
| | PACKAGE INCLUDES EXHAUST HOOD. |
| | ADDITIONAL INFORMATION OR TESTING MAY BE |
| | REQUIRED BY THE BUILDING OFFICIAL TO |
| | SUPPORT STATEMENT FROM ALFRESCO GRILLS |
| | LETTER. SEC. 104.2.1.2 CITY AMENDMENTS |
| | TO FBC 2001. |
| | |
| | 7- DESIGN PARAMETERS ON SHEET A-3: |
| | CLARIFY WHERE IS THE BASIC VELOCITY |
| | PRESSURE TAKEN FROM. THERE ARE NOT |
| | TABLES REFERENCED IN CHAPTER 16 FBC |
| | 2001. (THIS WAS THE STANDARD BUILDING |
| | CODE TABLE NOT THE FBC). SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | |
| | 8- EXTERIOR ELEVATIONS CALL FOR FLAT |
| | CEMENT TILE. PRODUCT APPROVAL SUBMITTED |
| | IS FOR "S" TILE. CLARIFY/REVISE AS REQ'D |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT (561)805-6712. |