| 2005-03-10 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- MISSING SHEET A-2. |
| | |
| | 2- A/C AREA WAS INCREASED. NEED TO BRING |
| | DWGS TO THE PALM BEACH COUNTY TO UPDATE |
| | INFORMATION AND RE-STAMP DRAWINGS AND |
| | PAID RECEIPT. |
| | |
| | 3- PLANS WERE REVISED ADDING A/C AREA. |
| | REVISE THE ENERGY CALCULATIONS |
| | ACCORDINGLY. |
| | |
| | 4- UPDATE/REVISE TRUSS ANCHOR SCHEDULE |
| | TO MATCH CAPACITY AND TYPE & NUMBER OF |
| | NAILS PUBLISHED ON THE FLORIDA PRODUCT |
| | APPROVAL. OTHERWISE, PROVIDE COMPLETE |
| | ENGINEERING ANALYSIS AND CALCULATIONS |
| | THAT COMPLY WITH SECTION 1609.4.3 FBC |
| | WHERE THE STRESS INCREASE IS NO ALLOWED. |
| | |
| | 5- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR: |
| | A) ENTRY DOORS. VERIFY SIZE AND SWING |
| | DIRECTION ON PLANS. ALSO, NEED TO BE |
| | SOLID OR HAVE IMPACT GLASS IF THIS IS |
| | THE DOOR USED FOR EMERGENCY EGRESS AS |
| | REQ'D BY SEC. 1005.4.5 FBC 2001. |
| | |
| | B) FRENCH DOOR. SEE SIZES ON PLANS. |
| | |
| | 5- SHEET A-3 NOTE CALLS FOR IMPACT |
| | GLAZING IN ALL DOORS AND WINDOWS. BUT, |
| | STORM SHUTTERS INFORMATION IS SUBMITTED. |
| | REVISE PLANS AS REQUIRED TO MATCH |
| | PROTECTION OF GLASS BY SHUTTERS OR |
| | IMPACT GLASS IN DOORS AND WINDOWS. |
| | |
| | 6- BBQ SPECS SAY THAT GRILLWAS |
| | DESIGNED FOR OUTDOOR USE ONLY & CANN'T |
| | BE INSTALLED IN THE BUILDING AND BELOW |
| | OVERHEAD UNPROTECTED CONSTRUCTION. |
| | PROVIDE CERTIFICATION FROM MANUFACTURER |
| | THAT BBQ GRILL WILL BE OK TO INSTALL IN |
| | THE PORCH. SEC. 2808 FBC 2001. |
| | |
| | 7- STORM SHUTTERS: A) ENGINEER'S GENERAL |
| | NOTE #6 REQUIRES DRAWINGS TO BE SIGNED, |
| | SEALED AND DATED BY HIM. |
| | |
| | B) THERE ARE SOME PANELS THAT EXCEED |
| | MAX. PANEL SPAN ACCORDING TO THE DESIGN |
| | PRESSURES. REVISE AS REQUIRED. |
| | |
| | C) CLEARLY MARK ON ENGINEERED DRAWINGS |
| | ANCHOR SCHEDULE SPECIFIC ANCHOR TO BE |
| | USED ACCORDING TO THE EDGE DISTANCE, |
| | DESIGN PRESSURES, PANEL SPAN, CONNECTION |
| | TYPE AND STRUCTURE TO BE ATTACHED TO |
| | (MASONRY OR 2500PSI CONCRETE). |
| | |
| | 8- NOTICE OF COMMENCEMENT EXPIRES AFTER |
| | 90 DAYS WITHOUT WORK. NEED RE-RECORDED |
| | NOTICE OF COMMENCEMENT. |
| | |
| | 9- OWES $83.45 FOR INCREASED A/C AREA. |
| | |