| 2005-01-31 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- PROVIDE COMPLETE BATHROOM WITH DOOR |
| | THAT ALLOWS 29" MIN. CLEAR OPENING. |
| | SECTION 11-11 FBC 2001. |
| | |
| | 2- SPECIFY ROOF TILE FASTENING. SECTION |
| | 104.2.1.1 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 3- UPDATE TRUSS ANCHOR SCHEDULE. |
| | PROVIDE |
| | COMPLETE ENGINEERING CALCULATIONS FOR |
| | TYPE AND NUMBER OF FASTENERS THAT |
| | DIFFER |
| | FROM THOSE TESTED AND PUBLISHED BY |
| | MANUFACTURER TO COMPLY WITH SECTION |
| | 1609.4.3 FBC 2001. |
| | |
| | 4- A) NEED NAME OF ARCHITECT WHO IS |
| | SEALING THE PLANS. CHAPTER 61G1-16004 |
| | FAC. |
| | B) STATE REGISTRATION NUMBER IS |
| | INCORRECT. REVISE AS REQUIRED. |
| | |
| | 5- PROVIDE COMPLETE DETAIL/SPECS FOR |
| | CEILING INSTALLATION AT ENTRY AND REAR |
| | PORCHES. SPECIFY FASTENERS SIZE AND |
| | SPACING. SEE ASTM C926 AND ASTM C1063. |
| | SECTION 2504.2 FBC 2001. |
| | |
| | 6- OWNER/AGENT TO SIGN AND DATE THE |
| | ENERGY CALCULATIONS. |
| | |
| | 7- PROVIDE FLORIDA OR APPLY FOR LOCAL |
| | PRODUCT APPROVAL FOR: |
| | A) ENTRY DOORS. |
| | B) FRENCH DOORS. |
| | C) CONCRETE LINTELS: NEED EXACT DADE |
| | COUNTY NOA THAT MATCHES ONE SUBMITTED |
| | FOR FLORIDA LOCAL APPROVAL. |
| | D) FIXED WINDOWS THAT MEET THE SIZES |
| | AND |
| | DESIGN PRESSURES SHOWN ON PLANS. |
| | E) ARABESQUE WINDOW. SEE PLANS. |
| | |
| | 8- A) PROVIDE COMPLETE UL LISTING AND |
| | SPECS FOR FIREPLACE. SEC. 2806 FBC |
| | 2001. |
| | B) PROVIDE COMPLETE APPROVED BBQ SPECS. |
| | SECTION 2808 FBC 2001. |
| | |
| | 9- STORM SHUTTERS: A) KEY PLAN DOESN'T |
| | MATCH PLANS. |
| | B) REVISE MIN. PANEL SIZE. SEE |
| | ENGINEERED DRAWINGS FOR LIMITATIONS. |
| | C) REVISE INTERIOR AND END ZONES. SEE |
| | PLANS. |
| | D) REVISE DESIGN PRESSURES. SEE PLANS. |
| | |
| | 10- PROVIDE COMPLETE FRAMING DETAILS |
| | FOR |
| | ARABESQUE WINDOW. SECTION 104.2.1.2 |
| | CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 11- OWES $866.23 FOR UPDATED |
| | CALCULATION. |
| | |
| | 12- REVISE FOUNDATION NOTE #2 ON SHEET |
| | A-2. SEE CHAPTER 19 FBC 2001 FOR PROPER |
| | ACI REFERENCE. |
| | |
| | 13- REVISE CONNECTORS SPECIFIED ON |
| | DETAIL 2/A-9. "SEMCO" IS OUT OF |
| | BUSINESS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT (561)805-6712. |