Plan Review Notes
Plan Review Notes For Permit 04121835
Permit Number 04121835
Review Stop E
Sequence Number 4
Notes
Date Text
2005-09-02 00:00:00************ UNSAT ************
  
 1)NOTE: PLEASE LABEL ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULES
 SUBMITTED.
 PLEASE SEE MANY ITEMS NOT CIRCUITED.
 PLEASE SEE MANY ITMES CIRCUITED WHICH DO
 NOT CORRELATE WITH CIRCUITS SHOWN ON
 PLANS.( A-6, A-8 ETC)
 PLEASE LABEL "LITE-TOUCH" DEVICES ,
 ITEMS BEING FED FROM THESE PANELS.
  
 2)NOTE: PLEASE INCLUDE PANEL SCHEDULE
 FOR NEW PANEL "C".
 215.5
  
 3)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR EACH NEW PANEL.
 220.31, 215.5
  
 4)NOTE: PLEASE SEE 210.52C1 FOR MISSING
 KITCHEN COUNTERSPACE GFI'S.
  
 5)NOTE: PLEASE BE SURE TITLE BLOCK
 CONTAINS THE PRINTED NAME AND LICENSE #
 OF ARCH. FAC 61G1-16.004
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  