Plan Review Notes
Plan Review Notes For Permit 04121835
Permit Number 04121835
Review Stop P
Sequence Number 2
Notes
Date Text
2005-06-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. THE SANITARY RISER DIAGRAM DOES NOT
 REFLECT ALL CHANGES FROM EXISTING FLOOR
 PLAN TO NEW FLOOR PLAN. SHOW THE
 FOLLOWING ON THE RISER DIAGRAM:
 A. KITCHEN SINK LOCATION CHANGE
 B. MASTER BATH CHANGING TO PROWDER ROOM
 C. SHOWER BATH CHANGEING TO MASTER BATH
 D. BAR SINK ADDED. BAR SINK SHALL NOT
 DRAIN THROUGH THE WET VENT FOR THE
 BATHROOM FIXTURES. 909.1
 E. NEW LAVS ADD TO MASTER BATH
 F. NEW LAUNDRY SINK
 G. W/M RISER/TRAP/STANDPIPE CHANGED
 FROM ONE WALL TO ANOTHER.
 H. NEW BAR SINK BY WATER WALL.
 I. NEW SHOWER ADDED TO POWDER ROOM
 J. EXTRA LAV BATHROOM #2
 K. TUB CHANGED TO SHOWER BATHROOM #2
 SECTIONS 104.2.1 & 104.3.1.1.
 2. SUBMIT A WATER RISER DIAGRAM. SHOW
 PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS (REQUIRED BY 604.9) & POINTS
 OF CONNTECTION. SECTION 104.3.1.1.
 3. IN THE INSTALLATION OR REMOVAL OF ANY
 PART OF A DRAINAGE SYSTEM, DEAD ENDS
 SHALL BE PROHIBITED, SECTION 704.5
 4. MORE INFORMATION IS REQUIRED ON THE
 WATER WALL. SUBMIT A DETAIL. INDICATE IF
 A WATER SUPPLY IS ATTACHED. IF SO,
 BACKFLOW PROTECTION IS REQUIRED.
 INDICATE IF THERE IS DRAINAGE FOR THE
 WALL. IF SO INDICATE METHOD OF DRAINING
 THIS WATER FEATURE. SECTION 104.2.1.
 5. ALL DRAWINGS, INFORMATION,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 SECTION 104.2.1. (THIS IS FOR ALL SHEETS
 NOT SIGNED, SEALED, DATED BY A DESIGN
 PROFESSIONAL).
  
 REVIEW BY KEN STEVENS