2005-05-30 00:00:00DENIED:
 1. THE MASTER BEDROOM R/A PASSTHRU NOT
 SIZED PROPERLY.PER 2001 FBC/M 601.4
 EXCEPTION #2 & 3 TRANSFER GRILLES SHALL
 HAVE 50 SQUARE INCHES (OF GRILLE AREA)
 TO 100 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH THE WALL TRANSFER GRILLES.ALL
 AIR SUPPLY INTO THE MASTER SUITE IS TO
 BE INCLUDED FOR PROPER SIZING OF THE
 RETURN AIR. PER DEAN FLEMMING - RETURN
 AIR PLENUM.NEED FAN SHUT DOWN.
  
 2. INDICATE HOW THE RETURN AIR IS
 TRANSFERRED BACK TO THE AHU.
  
 3.PROVIDE ENERGY & MANUAL J
 CALCULATIONS PRE 2001 FBC CHAPTER 13
 SUB-CHAPTER 6. SPOKE WITH DEAN FLEMING
 (GENERAL CONTRACTOR), REMOVED 1 WALL TO
 COMBINE 2 UNITS, NO CHANGE IN EQUIPMENT
 DO NOT NEED ENERGY CALCULATIONS.
  