| Plan Review Notes For Permit 04121835 |
| Permit Number |
04121835 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-05-30 00:00:00 | DENIED: | | | 1. THE MASTER BEDROOM R/A PASSTHRU NOT | | | SIZED PROPERLY.PER 2001 FBC/M 601.4 | | | EXCEPTION #2 & 3 TRANSFER GRILLES SHALL | | | HAVE 50 SQUARE INCHES (OF GRILLE AREA) | | | TO 100 CFM (OF SUPPLY AIR) FOR SIZING | | | THROUGH THE WALL TRANSFER GRILLES.ALL | | | AIR SUPPLY INTO THE MASTER SUITE IS TO | | | BE INCLUDED FOR PROPER SIZING OF THE | | | RETURN AIR. PER DEAN FLEMMING - RETURN | | | AIR PLENUM.NEED FAN SHUT DOWN. | | | | | | 2. INDICATE HOW THE RETURN AIR IS | | | TRANSFERRED BACK TO THE AHU. | | | | | | 3.PROVIDE ENERGY & MANUAL J | | | CALCULATIONS PRE 2001 FBC CHAPTER 13 | | | SUB-CHAPTER 6. SPOKE WITH DEAN FLEMING | | | (GENERAL CONTRACTOR), REMOVED 1 WALL TO | | | COMBINE 2 UNITS, NO CHANGE IN EQUIPMENT | | | DO NOT NEED ENERGY CALCULATIONS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|