| Date |
Text |
| 2005-05-09 00:00:00 | ************** UNSAT ************* |
| | |
| | PLEASE SEE SAME COMMENTS AS PREVIOUS |
| | REVIEW. |
| | |
| | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH A PANEL |
| | SCHEDULE(S) TO BE SUBMITTED. |
| | 215.5 |
| | PLEASE SEE ALL MIN REQUIRED PER2002 |
| | NEC. |
| | |
| | |
| | 2)NOTE: PLEASE SEE 110.26 FOR CLEARENCE |
| | REQUIRED FOR PANEL. APPEARS TO BE SHOWN |
| | ABOVE KITCHEN COUNTERSPACE. |
| | THIS APPEARS TO RELOCATED FROM PREVIOUS |
| | REVIEW. |
| | |
| | 3)NOTE: PLEASE SHOW ANY EXISTING |
| | ELECTRICALTO MEET 2002 NEC. PLANS |
| | APPEAR TO SOME NEW ELECTRICAL BUT NOT |
| | CLEAR OF ALL IS TO BE NEW OR EXSITING? |
| | PLEASE SHOW ALL MIN REQUIRED UNDER 2002 |
| | NEC. |
| | PLEASE SEE 210.52,210.8,210.11 ETC |
| | PLEASE SEE 2002 NECIF ALL SHOWN IS |
| | NEW, PLEASE SEE THERE ARE NUMEROUS ITMES |
| | FOR NEC CODE COMPIANCE MISSING. |
| | PLEASE ALSO SEE FBC CHAPTER 34 FOR |
| | REMODEL WORK.3401.7.2 |
| | |
| | 4)NOTE: PLEASE SEE "LITE TOUCH" SYSTEM |
| | IS NOW BEING SHOWN FOR INSTALLATION. |
| | PLEASE PROVIDE MANUFACTURE SPEC/CUT |
| | SHEETS FOR THIS SHOWING THE NRTL |
| | LISTING. |
| | |
| | 5)NOTE: PLEASE SEE SEE COPY OF FS |
| | 553.80(2)(B) ATTACHED WITH RESPECT TO |
| | DESIGN PROFESSIONAL. THIS IS A NOTICE |
| | ONLY GIVEN AT THIS TIME. |
| | |
| | PLEASE BE SURE TO REMOVE ALL OLD/ VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STMAPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |