| Plan Review Notes For Permit 04121835 |
| Permit Number |
04121835 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-01-24 00:00:00 | 1) DEMOLITION, RENOVATION AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 2) DEBRIS SHALL BE REMOVED FROM SITE THE | | | SITE DAILY. | | | | | | 3) PLEASE SHOW SMOKE DETECTORS LOCATION | | | ON PLANS. | | | | | | 4) INTERIOR WALL AND CEILING FINISH | | | SHALL COMPLY WITH NFPA 101 LIFE SAFETY | | | CODE CHAPTER 30.3.3.2; CLASS A, CLASS | | | B, | | | OR CLASS C. | | | | | | 5) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE ALARM AND FIRE | | | SPRINKLER REMODELS. | | | | | | | | | NATE MCCRAY, CAPTAIN | | | 561-835-2910 OR 561-805-6722 |
|