| 2005-12-07 00:00:00 | ********* UNSAT *********** |
| | |
| | 1)NOTE: PLEASE SEE FOUNTAIN PUMP SHOWN |
| | WITH 20A OCP ON #14. |
| | |
| | 2)NOTE: PLEASE CORRELATE PANEL SCHEDULE |
| | FOR POOL PANEL AND PANEL "B" WITH RISER |
| | DIAGRAM. |
| | PLEASE SEE PANEL "B" SHOWS 100A OCP AND |
| | #2 TO POOL PANEL. POOL PANEL ON RISER IS |
| | SHOWN AS 80A OCP AND #4 AND POOL PANEL |
| | SCHEDULE SHOWS 60A ?? |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE WARMING DRAWER SHOWN |
| | ON PLANS, YET THIS IS NOT ON PANEL |
| | SCHEDULE OR ADDED TO LOAD CALCS. |
| | 215.5 |
| | |
| | 4)NOTE: PLEASE SEE SD IN MASTER BEDRM IS |
| | REQUIRED TO BE WITHIN 12"OF THE HIGHEST |
| | POINT OF A FLAT CEILING. |
| | PLEASE KNOW, IF TRAT CEILING IS 12" OR |
| | MORE ABOVE OTHER CEILING IN RM, THE SD |
| | WILL BE REQUIRED TO BE LOCATED IN TRAY |
| | CEILING AREA. |
| | NFPA-72 11.8.3.5 |
| | |
| | 5)NOTE: PLEASE CORRELATE THE NUMBER OF |
| | RECESSED LTS ON PLANS WITH THE # IN LOAD |
| | CALCS ETC. |
| | PLEASE SEE LOAD CALCS INDICATE A TOTAL |
| | OF 84, HOWEVER THERE ARE 125+ |
| | PLEASE ADJUST. |
| | 220.3B4 |
| | |
| | 6)NOTE: PLEASE CLARIFY NOTE FOR ALL |
| | "OUTLETS " IN BEDRMS TO HAVE ARC FAULT |
| | PROTECTION. THIS INCLUDES , SD', FANS, |
| | LTS, AND RECEPTS. |
| | 2002 NEC 210.12 |
| | IT IS KNOWN THAT THE RECEPTS ARE SHOWN |
| | AS AFCI, HOWEVER A AFCI RECEPT IS NOT |
| | KNOWN TO BE MADE AT THIS TIME. |
| | |
| | 7)NOTE: PLEASE SHOW LOCATION OF POOL |
| | PANEL ON PLANS. |
| | 215.5 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |