| Notes |
| Date |
Text |
| 2005-03-21 00:00:00 | *********UNSAT ******* | | | | | | PLEASE SEE NOTES FROM PREVIOUS REVIEW. | | | | | | 1)NOTE: NOTE #1, NO PLEASE CORRELATE | | | RISER DIAGRAM AND PANELS. | | | PLEASE SEE PANEL "A" IS SHOWN FEEDING | | | SUB-PANEL "C" , RISER SHOWS PANEL "B"? | | | PLEASE SEE PANEL "C" IS SHOWN AS 80A | | | AND RISER SHOWS AS 150A? | | | PLEASE SEE RISER MENTIONS FEED FOR SUB | | | PANEL WITH 4#12'S ALONG WITH FEEDER?? | | | | | | 2)NOTE: PLEASE SEE FOUNTAIN PUMP SHOWN | | | AS 2P20 ON #14 AWG. | | | | | | 3)NOTE: PLEASE SEE BLOWER IS SHOWN AS | | | GAS FOR POOL?? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | 2005-03-18 00:00:00 | IN FOR REVIEW. PLANS UNSAT, NOTES TO | | | FOLLOW. |
|