| 2005-03-28 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)FROM PREVIOUS NOTE #4 THE BEDROOM |
| | IS NOW LABELED "OFFICE", BUT THE PLANS |
| | ARE STILL LABELED "MODEL NAPA W/GUEST |
| | HOUSE".TO AVOID CONFUSION, AND AS THIS |
| | IS A LIFE SAFETY ISSUE (SMOKE |
| | DETECTORS), PLEASE EITHER REMOVE "GUEST |
| | HOUSE" REFERENCE FROM PLAN OR INDICATE |
| | WHICH PART OF THE HOUSE IS THE GUEST |
| | HOUSE. |
| | |
| | 2.)SOME OF THE DESIGN STANDARDS WERE |
| | CHANGED BUT ARE NOT CURRENT OR |
| | REFERENCED IN THE FBC.SPECIFICALLY, |
| | ACI-95 (CONCRETE UNIT MASONRY, H AND |
| | WIND LOADS) SHOULD BE ACI-02.TRUSSES, |
| | D, REFERS TO TPI85. I WAS UNABLE TO |
| | LOCATE PCT80 AND BWT76 ON THE TPI |
| | WEBSITE.ARE THEY PRODUCED BY ANOTHER |
| | ORGANIZATION?PLEASE SEE BCSI 1 BY TPI |
| | WHICH ADDRESSES BRACING AND DESIGN. |
| | PLEASE CHECK ALL STANDARDS, FBC35. |
| | |
| | 3.)SEE PREVIOUS LIST, ITEM #11. |
| | NAILING CONFLICTS WITH THE CATALOG. |
| | VALUES USED SHOULD BE CONSISTENT WITH |
| | THE PAPERWORK ON THE FLORIDA WEBSITE |
| | WWW.FLORIDABUILDING.ORG.IF FASTENING |
| | SPECIFIED IS NOT CONSISTENT WITH |
| | MANUFACTURER'S SPECIFICATION, APPLY FOR |
| | A LOCAL PRODUCT APPROVAL PURSUANT TO |
| | FAC9B72 WITH CALCULATIONS AS PER |
| | ASSISTANT BUILDING OFFICIAL. |
| | |
| | 4.)FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVAL REQUIRED FOR THE FLEETWOOD |
| | WINDOWS & DOORS, FAC9B72. |
| | WWW.FLORIDABUILDING.ORG |