| 2005-02-02 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)THE OWNER INFORMATION DOESN'T |
| | MATCH |
| | OUR RECORDS. |
| | |
| | 2.)THE NOC IS EXPIRED, MORE THAN 90 |
| | DAYS WITHOUT COMMENCING WORK, |
| | FS713.13(2). |
| | |
| | 3.)A3, THE NOTE REGARDING THE 10# LL |
| | IS NOT IN COMPLIANCE WITH FBC TABLE |
| | 1604.1.ATTICS WITH STORAGE ARE TO |
| | HAVE |
| | A 30# BCLL.ROOF FRAMING PLAN SHOWS |
| | 10# |
| | FOR STORAGE AREAS (TWO NOTES). |
| | |
| | 4.)THE FLOOR PLAN SHOWS THE ROOM |
| | ADJACENT TO THE CABANA AS AN OFFICE, |
| | ROOF FRAMING PLAN SHOWS IT AS A GUEST |
| | ROOM.IS THIS AREA THE "GUEST HOUSE" |
| | REFERRED TO ON THE PLAN?SLEEPING |
| | ROOMS |
| | ARE TO HAVE SMOKE DETECTORS IN |
| | COMPLIANCE WITH FBC 905.2.2. |
| | |
| | 5.)THE TWO SETS OF PLANS SUBMITTED |
| | HAVE DIFFERENT SIGNATURES AND DATES. |
| | |
| | 6.)SHEET T1, CONCRETE UNIT MASONRY, H |
| | REFERS TO A CODE FOR HVHZ.CITY OF WPB |
| | IS NOT IN THE HVHZ.PLEASE CORRECT |
| | REFERENCES (ACI REFERENCES ARE |
| | DIFFERENT |
| | FOR HVHZ AS WELL). |
| | |
| | 7.SHEET T1, WIND LOADS (DESIGN |
| | PARAMETERS), REFERS TO A STANDARD FOR |
| | WOOD CONSTRUCTION WHICH I AM UNABLE TO |
| | LOCATE IN THE FBC. |
| | |
| | 8.)A6, KNEE WALL ON GIRDER TRUSS, |
| | REFERS TO HUGHES CONNECTORS.THEY HAVE |
| | BEEN OUT OF BUSINESS FOR YEARS. |
| | SPECIFY |
| | ONLY AVAILABLE PRODUCTS. |
| | |
| | 9.)A3 (AT GARAGE) REFERS TO AHU |
| | INSTALLATION DETAIL ON SHEET 9, BUT |
| | THERE IS NO SHEET 9. |
| | |
| | 10.) ROUGH CARPENTRY NOTES (U), SHEET |
| | T1, SPECIFIES 5/8" PLYWOOD WHICH |
| | CONFLICTS WITH THE DETAILS. |
| | |
| | 11.) A3, USP ANCHOR SCHEDULE, HTA20, |
| | NAILING CONFLICTS WITH CATALOG. |
| | ALLOWABLE LATERAL LOAD ON PLAN EXCEED |
| | PRODUCT LIMITATIONS.CHECK ALL |
| | CONNECTORS. |
| | |
| | 12.)FLORIDA OR LOCAL PRODUCT |
| | APPROVALS |
| | REQUIRED FOR ALL PRODUCTS, USP ANCHOR |
| | SCHEDULE.SOME REFER TO NOAS. |
| | WWW.FLORIDABUILDING.ORG. |
| | |
| | 13.) THERE ARE NOTES ON THE FLOOR PLAN |
| | FOR TEMPERED GLASS, BUT ANOTHER NOTE ON |
| | THE PLAN INDICATES THAT ALL WINDOWS |
| | WILL |
| | BE IMPACT.SOME PRODUCT APPROVALS |
| | SUBMITTED ARE FOR NONIMPACT PRODUCTS. |
| | ADDRESS.FOR PRODUCT APPROVALS |
| | COVERING |
| | SEVERAL PRODUCTS, INDICATE THE PRODUCT |
| | YOU ARE USING. |
| | |
| | 14.)IMPACT PROTECTIONS REQUIRED |
| | FBC1606.1.4.IF GLAZING IS NOT IMPACT, |
| | PROVIDE PRODUCT APPROVALS AND HURRICANE |
| | SHUTTER INSTALLATION SCHEDULE OR A |
| | SEPARATE PERMIT FOR SHUTTERS WILL BE |
| | REQUIRED.CHANGE THE NOTES ON THE |
| | PLAN. |
| | |
| | 15.)THE GARAGE JAMB DETAIL, A6, |
| | CONFLICTS WITH THE PRODUCT APPROVAL. |
| | |
| | 16.)A6, WINDOW & SGD JAMB DETAIL, |
| | SPECIFY BUCK ATTACHMENT (LENGTH). |
| | |
| | 17.)THE PLAN SPECIFIES CLAY BARREL |
| | TILE (A6), PRODUCT APPROVAL SUBMITTED |
| | IS |
| | FOR CONCRETE TILE. |
| | |
| | 18.)THE TEST REPORT FOR THE ENTRY IS |
| | FOR GLAZED AND OPAQUE DOORS. |
| | FBC1005.4.5 REQUIRES A MEANS OF ESCAPE |
| | IN THE EVENT OF TEMPORARY INSTALLATION |
| | OF HURRICANE PROTECTION.IS THE FRONT |
| | DOOR GLAZED OR OPAQUE? |
| | |
| | 19.)CASEMENT WINDOWS IN A 26 SIZE |
| | WERE |
| | SPECIFIED ON THE PLAN; PGT IMPACT |
| | PRODUCT APPROVALS SUBMITTED.THE |
| | WINDOWS ARE UNAVAILABLE IN THIS SIZE. |
| | ADDRESS. |
| | |
| | 20.)FAC9B72, FLORIDA STATE OR LOCAL |
| | PRODUCT APPROVAL REQUIRED FOR ALL |
| | PRODUCTS.WWW.FLORIDABUILDING.ORG |
| | |
| | |