Plan Review Notes
Plan Review Notes For Permit 04121828
Permit Number 04121828
Review Stop P
Sequence Number 1
Notes
Date Text
2005-02-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) CLEANOUTS ARE REQUIRED NEAR THE
 JUNCTION OF THE BUILDING DRAIN AND THE
 BUILDING SEWER. SECTION 708.3.5. (SEE
 THE LINES TO THE MASTER BATH STACK, THE
 WASH MACHINE AND THE POWDER ROOM/KITCHEN
 SINK BUILDING DRAIN LINES.
 2) ALL DRAWINGS SHALL BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN. SIGNATURE STAMPS ARE NOT
 ACCEPTABLE. SIGNATURE IS REQUIRED.
 SECTION 104.2.1.
  
  