| Plan Review Notes For Permit 04121828 |
| Permit Number |
04121828 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-02-10 00:00:00 | DENIED: | | | 1.PLAN SHEET A/2 INDICATES A GAS WATER | | | HEATER SHARING THE CLOSET WITH THE AHU. | | | PER 2001 FBC(M)603.9, COMBUSTION WATER | | | HEATERS SHALL NOT BE LOCATED IN | | | MECHANICAL CLOSETS USED AS RETURN AIR | | | PLENUMS. | | | | | | 2.PLAN SHEET A/2 INDICATES A GAS | | | DRYER.PROVIDE CALCULATIONS FOR | | | COMBUSTION AIR IN ACCORDANCE WITH 2001 | | | FBC(M) CHAPTER 7. | | | | | | 3.INDICATE ON THE PLAN METHOD OF | | | MAKE-UP AIR. | | | | | | 4.PROVIDE SUBMITTAL DATA FOR ALL GAS | | | APPLIANCES. | | | | | | 5.PLAN SHEET A/8, PLAN DOES NOT | | | INDICATE ANY RETURN AIR FROM NEW GYM AND | | | SUNROOM AREAS.PLEASE SHOW COMPLIANCE | | | WITH 2001 FBC(M)601.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|