| Plan Review Notes For Permit 04121828 |
| Permit Number |
04121828 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-02-09 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THERE ARE SEVERAL AREAS THAT DO NOT | | | COMPLY WITH THE SPACING REQUIREMENTS OF | | | 210.52, SUN RM, GREAT ROOM, BED ROOM & | | | FAMILY ROOM. SEE REVIEWED PLAN. | | | | | | 2} SMOKE DETECTORS ARE REQUIRED PER | | | ARTICLE 8-1.4.1.6.2 NFPA-72,STAIRS AND | | | MASTER BEDROOM. | | | | | | 3} SEE 210.63 FOR RECEPTACLE @ | | | EQUIPMENT | | | RE: A/C CONDENSOR(S). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|