| Date |
Text |
| 2006-10-06 00:00:00 | ***** UNSAT ***** |
| | |
| | 1) NOTE: PLEASE SEE RISER IS SHOWING |
| | DISONNECT AS WHAT IS REALLY AND "PANEL" |
| | FOR THE HWH. PLEASE INDICATE ON RISER AS |
| | "PANEL HWH", AND ON PANEL "B" SCHEDULE |
| | "PANEL HWH" OR ANY LABELING WHICH CALLS |
| | FOR THIS BEING A PANEL. |
| | PLEASE SEE NO DISCONNECTING MEANS IS |
| | BEING SHOWN FOR THE UNIT. THE PANEL IS |
| | LOCATED IN THE HALL WHICH IS OK, HOWEVER |
| | IS NOT WITHINSIGHT OF UNIT FOR |
| | DISCONNECTING MEANS. |
| | 422.31, 422.31. |
| | PLEASE SEE KNOW, MIN CLEARENCES STILL |
| | MUST BE MET FOR UNIT(S) FROM |
| | COMBUSTIBLES AS REQUIRED PER |
| | MANUFACTURES SPEC(THIS IS TO BE |
| | VERIFIED). |
| | |
| | ** PLEASE KNOW, ANY USE OF BREAKERS FOR |
| | A MEANS OF DISCONNECT, PLEASE KNOW THE |
| | "LOCK-OFF" DEVICE, MUST BE AN "INTEGRAL" |
| | PART OF THE BREAKER. THE "SNAP" ON |
| | DEVICES WHICH READILY FALL OFF ARE NOT |
| | PERMITTED OR ACCEPTABLE. |
| | |
| | ** PLEASE SEE THEN KW RATING ON LOAD |
| | CALCS AND DISC/PANEL HWH SHOW TWO |
| | DIFFERENT LOADS. |
| | PLEASE CORRELATE. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |