Plan Review Notes
Plan Review Notes For Permit 04121827
Permit Number 04121827
Review Stop E
Sequence Number 9
Notes
Date Text
2006-10-06 00:00:00***** UNSAT *****
  
 1) NOTE: PLEASE SEE RISER IS SHOWING
 DISONNECT AS WHAT IS REALLY AND "PANEL"
 FOR THE HWH. PLEASE INDICATE ON RISER AS
 "PANEL HWH", AND ON PANEL "B" SCHEDULE
 "PANEL HWH" OR ANY LABELING WHICH CALLS
 FOR THIS BEING A PANEL.
 PLEASE SEE NO DISCONNECTING MEANS IS
 BEING SHOWN FOR THE UNIT. THE PANEL IS
 LOCATED IN THE HALL WHICH IS OK, HOWEVER
 IS NOT WITHINSIGHT OF UNIT FOR
 DISCONNECTING MEANS.
 422.31, 422.31.
 PLEASE SEE KNOW, MIN CLEARENCES STILL
 MUST BE MET FOR UNIT(S) FROM
 COMBUSTIBLES AS REQUIRED PER
 MANUFACTURES SPEC(THIS IS TO BE
 VERIFIED).
  
 ** PLEASE KNOW, ANY USE OF BREAKERS FOR
 A MEANS OF DISCONNECT, PLEASE KNOW THE
 "LOCK-OFF" DEVICE, MUST BE AN "INTEGRAL"
 PART OF THE BREAKER. THE "SNAP" ON
 DEVICES WHICH READILY FALL OFF ARE NOT
 PERMITTED OR ACCEPTABLE.
  
 ** PLEASE SEE THEN KW RATING ON LOAD
 CALCS AND DISC/PANEL HWH SHOW TWO
 DIFFERENT LOADS.
 PLEASE CORRELATE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  