| 2006-09-28 00:00:00 | ********** UNSAT *********** |
| | |
| | ***** PLEASE SEE ELECTRICAL RISER |
| | DIAGRAM HAS NOW BEEN COMPLETELY REVISED |
| | WHICH IS NOT CODE COMPLIANT. |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE RISER NOW SHOWS THE |
| | DISCONNECT ON THE LOAD SIDE OF THE ATS |
| | AS 100A'S, WHEN THE OCP AND LOAD THROUGH |
| | THIS DISCONNECT IS GREATER AND EXCEEDS |
| | THAT OF ITS RATING. |
| | 240. 408 ETC. |
| | |
| | 2) NOTE: PLEASE SEE NOW A NEW PANEL "C" |
| | IS BEING INTRODUCED BEING FED FROM THE |
| | GARAGE WHICH IS A DETACHED BLUIDING. |
| | PLEASE SEE THIS PANEL IS BEING SHOWN |
| | UPSTAIRS AND MLO. |
| | PLEASE SEE THIS IS NOT PERMITTED. |
| | PLEASE SEE 225.31-225.39. |
| | PLEASE ALSO SEE THIS PANEL IS BEING |
| | SHOWN AS NO MEETING 110.26. |
| | |
| | 3) NOTE: PLEASE SEE LOAD ON PANEL "C" |
| | FOR TANKLESS WATER HEATER DOES NOT |
| | CORRELATE WITH LOAD CALCULATIONS. |
| | 220.31 |
| | |
| | 4) NOTE: PLEASE COMPLETE AND PROVIDE |
| | LOADCALULATIONS ON EACH OF THE PANELS |
| | AS SHOWN.220.31, 215.5 |
| | FBC106.1.2 ADMIN SECT. |
| | |
| | 5) NOTE: PLEASE SEE 250.32, 250.50 FOR |
| | NON COMPLIANCE FOR NEW PANEL. |
| | |
| | |
| | ** PLEASE KNOW, BASED ON THE NEW REVISED |
| | PLANS SUBMITTED, IT IS THE HOPE OF THIS |
| | OFFICE THAT THE INSTALLATION IN FIELD IS |
| | NOT WHAT IS SHOWN ON PLANS. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |