| 2006-09-19 00:00:00 | ****** UNSAT 3RD REVIEW OF REVSIONS*** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW. |
| | |
| | REVIEW FOR REV #5 AND 6. |
| | |
| | 1) NOTE: PLEASE SEE LOAD FOR TANKLESS |
| | WATER HEATER IS NOW BEING SHOWN AT |
| | 27KVA?? < YET, PLEASE SEE OCP IS STIL |
| | BEING SHOWN AT 100A'S? |
| | LOAD WAS INCREASED, YET THE OCP IS NOW |
| | NOT LARGE ENOUGH FOR THE NEW 27KW SHOWN. |
| | PLEASE ALSO SEE PLANS SHOW A "GAS " |
| | UNIT? IS THE UNIT #1, AS THE ONE LOCATED |
| | ON THE PANEL SCHEDULE IS UNIT #2.?? |
| | PLEASE SEELOAD CALCULATIONS STILL DO |
| | NOT SHOWN THIS 27KW LOAD. |
| | 220.31,240.4,310.16, ETC. |
| | |
| | 2) NOTE: PLEASE SEE PANELS A AND B IN |
| | MAIN HOUSE APPEARS TO SHOW SOME SORT OF |
| | COUNTER /WALL OR SOMETHING LOCATED IN |
| | FRONT OF THESE. PLEASE SEE 110.26.240.24 |
| | 408.7 ETC. |
| | |
| | 3) NOTE: PLEASE SEE NOT ALL SHEETS ARE |
| | SEALED BY THE ARCHITECT. |
| | FBC 106.1, FS 481.221 |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |