Plan Review Notes
Plan Review Notes For Permit 04121827
Permit Number 04121827
Review Stop E
Sequence Number 7
Notes
Date Text
2006-09-19 00:00:00****** UNSAT 3RD REVIEW OF REVSIONS***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW.
  
 REVIEW FOR REV #5 AND 6.
  
 1) NOTE: PLEASE SEE LOAD FOR TANKLESS
 WATER HEATER IS NOW BEING SHOWN AT
 27KVA?? < YET, PLEASE SEE OCP IS STIL
 BEING SHOWN AT 100A'S?
 LOAD WAS INCREASED, YET THE OCP IS NOW
 NOT LARGE ENOUGH FOR THE NEW 27KW SHOWN.
 PLEASE ALSO SEE PLANS SHOW A "GAS "
 UNIT? IS THE UNIT #1, AS THE ONE LOCATED
 ON THE PANEL SCHEDULE IS UNIT #2.??
 PLEASE SEELOAD CALCULATIONS STILL DO
 NOT SHOWN THIS 27KW LOAD.
 220.31,240.4,310.16, ETC.
  
 2) NOTE: PLEASE SEE PANELS A AND B IN
 MAIN HOUSE APPEARS TO SHOW SOME SORT OF
 COUNTER /WALL OR SOMETHING LOCATED IN
 FRONT OF THESE. PLEASE SEE 110.26.240.24
 408.7 ETC.
  
 3) NOTE: PLEASE SEE NOT ALL SHEETS ARE
 SEALED BY THE ARCHITECT.
 FBC 106.1, FS 481.221
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  