Plan Review Notes
Plan Review Notes For Permit 04121827
Permit Number 04121827
Review Stop E
Sequence Number 6
Notes
Date Text
2006-04-13 00:00:00** UNSAT **
  
 PLEASE SEE SOME NOTE FROM PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF
 CORECTING.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
  
 *********** UNSAT *****************
  
  
 1) NOTE: OK
  
 2) NOTE: OK.
  
 3) NOTE: OK
  
 4) NOTE:NO, PLEASE SEE SIZE HAS NOT
 INCREASED AND PLEASE SEE MULTIPLE
 LOCATIONS OF ATTACHMENT SHOWN ON RISER..
 PLEASE SEE 250.6,250.24B.
  
 ** PRE-NOTE**
 PLEASE SEE THE EXISTING
 GROUNDING ELECTRODE CONDUCTOR IS NO
 LONGER LARGE ENOUGH DUR TO THE INCREASE
 OF SERVICE. PLEASE SEE TABLE IN250.66
 AND ADJUST.
  
 5)NOTE: OK.
  
 6) NOTE: OK
  
 7) NOTE: OK.
  
 8) NOTE:NO, PLEASE SEE NO CHANGE WAS
 MADE TO THE KVA LOADS ON PANEL SCHEDULE
 OR IN LOAD CALCS.
  
 ** PRE- NOTES**
 PLEASE SEE 100A BRKR IS BEING
 SHOWN FOR NEW ELECTRIC TANKLESS UNIT,
 HOWEVER THE LOAD IS SHOWN AS 1.2VA PER
 PHASE AND IS NOT SHOWN IN LOAD CALCS.
 THIS WILL GREATLY AFFECT LOAD CALCS.
 215.5, 220
  
 9) NOTE: OK
  
 10) NOTE: OK
  
 11) NOTE:
  
 12) NOTE:
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  