| 2006-03-24 00:00:00 | *********** UNSAT ***************** |
| | |
| | |
| | 1) NOTE: PLEASE SEE PLANS ARE COMING IN |
| | WITH HAND DRAWN CHANGES MADE ON PLANS |
| | WHICH ARE SIGNED, DATED AND SEALED BY AN |
| | ARCHITECT WHICH IS NOT PERMITTED UNDER |
| | FS 481.221 |
| | PLEASE REVISE, RE-PRINT AND HAVE |
| | ARCHITECT SIGN,DATE AND SEAL PLANS. |
| | |
| | 2) NOTE: PLEASE SEE RISER IS COMING IN |
| | COMPLETELY DIFFERENT FROM PREVIOUS |
| | PLANS. PLEASE SEE NOW, SERVICE HAS BEEN |
| | INCREASED FROM THE PREVIOUS 300A'S TO |
| | NOW A 500A SERVICE. PLEASE SEE EXST, |
| | PREVIOUS SEC'S WERE SHOWN AS 350 MCM'S, |
| | HOWEVER THESE CONDUCTORS HAVE NOW BEEN |
| | REMOVED FROM THE PLANS. |
| | PLEASE SHOW THE SIZE OF THE NEW SEC'S IN |
| | RISER AND THE INCREASE OF THE SIZE OF |
| | RISER. PLEASE SHOW THE CONDUCTORS NOW |
| | BEING USED FROM THE GUTTER TO THE NEW |
| | MAINS AND EXIST. |
| | PLEASE INCLUDE THE SIZE OF THE GUTTER, |
| | IS THE EXST ONE LARGE ENOUGH? SHOW NEW |
| | SIZE. |
| | 240.4,310.15B6, 215.5 |
| | |
| | 3) NOTE: PLEASE SUBMITAIC RATINGS FOR |
| | NEW EQUIPMENT. |
| | 215.5,110.9 |
| | |
| | 4) NOTE: PLEASE SEE THE EXISTING |
| | GROUNDING ELECTRODE CONDUCTOR IS NO |
| | LONGER LARGE ENOUGH DUR TO THE INCREASE |
| | OF SERVICE. PLEASE SEE TABLE IN250.66 |
| | AND ADJUST. |
| | |
| | 5)NOTE: PLEASE SEE NEW PLANS DO NOT |
| | GROUP MAINS AT MAIN HOUSE AS REQUIRED |
| | PER 225.34. PLEASE SEE PLANS INDICATE |
| | ONE MAIN UPSTAIRS AND ONE DOWNSTAIRS???? |
| | PLEASE SEE ORIG PLANS CALLED FOR ONE |
| | PANEL, (EXIST) |
| | IT IS THIS OFFICE'S HOPE THIS IS NOT |
| | INSTALLED THIS WAY. |
| | PLEASE ALSO SEE THE EFFECT THIS WOULD |
| | AHVE FOR LOCATION OF GROUNDING THE |
| | SYSTEM AT THE MAIN HOUSE FOR THE NEW |
| | MAINS WHICH WILL BE REQUIRED. 250.32 |
| | |
| | 6) NOTE: PLEASE SEE MIN OCP FORAHU'S |
| | TO BE 125%. 424.3B, PLEASE SEE 50A OCP |
| | FOR 10KW UNIT. |
| | |
| | 7) NOTE: PLEASE SEE MIN VA FOR LAUNDRY / |
| | WASHER CIRCUIT. 210.11C2, 220.16B |
| | 1.5MIN |
| | |
| | 8) NOTE: PLEASE SEE 100A BRKR IS BEING |
| | SHOWN FOR NEW ELECTRIC TANKLESS UNIT, |
| | HOWEVER THE LOAD IS SHOWN AS 1.2VA PER |
| | PHASE AND IS NOT SHOWN IN LOAD CALCS. |
| | THIS WILL GREATLY AFFECT LOAD CALCS. |
| | 215.5, 220 |
| | |
| | 9) NOTE: PLEASE SEE REDLINED PLANS FOR |
| | LOAD CALCULATIONS FROM PREVIOUS PLANS |
| | PER 220.31B |
| | |
| | 10) NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52 , SOME OF THESE WERE REMOVED FROM |
| | PREVIOUS PLANS AND SOME WHICH WERE |
| | REDLINED FROM ORIG PLANS ARE STILL NOT |
| | IMPLEMENTED INTO PLANS. |
| | |
| | 11) NOTE: PLEASE SEE MANY AREAS/ROOMS |
| | WHERE THE REQUIRED EGRESS LT FIXTURE IS |
| | KNOW ONLY SHOWN AS A "J-BOX" , PLEASE |
| | KNOW, A MIN FIXTURE OF SOME SORT WILL BE |
| | REQUIRED FOR MIN EGRESS. 210.70, |
| | NFPA-101 7.8 |
| | PLEASE REVISE PLANS. |
| | |
| | 12) NOTE: PLEASE VERIFY THE MAINS AND |
| | SPACES AT THE 400A METER/MAIN. PLEASE |
| | KNOW, NO MORE THAN 6 MAINS ARE |
| | PERMITTED, PLEASE ALSO SEE NO MORE THAN |
| | 5 SPACES WOULD BE PERMITTED IN |
| | METER/MAIN. PLEASE PROVIDE SCHEDULE FOR |
| | M/M OR PROVIDE INFORMATION IS INDEED |
| | THERE IS A 400A MAIN BRKR. |
| | 230.70, 230.71 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLANREVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| 2006-03-23 00:00:00 | NOTES |