2006-03-24 00:00:00*********** UNSAT *****************
  
  
 1) NOTE: PLEASE SEE PLANS ARE COMING IN
 WITH HAND DRAWN CHANGES MADE ON PLANS
 WHICH ARE SIGNED, DATED AND SEALED BY AN
 ARCHITECT WHICH IS NOT PERMITTED UNDER
 FS 481.221
 PLEASE REVISE, RE-PRINT AND HAVE
 ARCHITECT SIGN,DATE AND SEAL PLANS.
  
 2) NOTE: PLEASE SEE RISER IS COMING IN
 COMPLETELY DIFFERENT FROM PREVIOUS
 PLANS. PLEASE SEE NOW, SERVICE HAS BEEN
 INCREASED FROM THE PREVIOUS 300A'S TO
 NOW A 500A SERVICE. PLEASE SEE EXST,
 PREVIOUS SEC'S WERE SHOWN AS 350 MCM'S,
 HOWEVER THESE CONDUCTORS HAVE NOW BEEN
 REMOVED FROM THE PLANS.
 PLEASE SHOW THE SIZE OF THE NEW SEC'S IN
 RISER AND THE INCREASE OF THE SIZE OF
 RISER. PLEASE SHOW THE CONDUCTORS NOW
 BEING USED FROM THE GUTTER TO THE NEW
 MAINS AND EXIST.
 PLEASE INCLUDE THE SIZE OF THE GUTTER,
 IS THE EXST ONE LARGE ENOUGH? SHOW NEW
 SIZE.
 240.4,310.15B6, 215.5
  
 3) NOTE: PLEASE SUBMITAIC RATINGS FOR
 NEW EQUIPMENT.
 215.5,110.9
  
 4) NOTE: PLEASE SEE THE EXISTING
 GROUNDING ELECTRODE CONDUCTOR IS NO
 LONGER LARGE ENOUGH DUR TO THE INCREASE
 OF SERVICE. PLEASE SEE TABLE IN250.66
 AND ADJUST.
  
 5)NOTE: PLEASE SEE NEW PLANS DO NOT
 GROUP MAINS AT MAIN HOUSE AS REQUIRED
 PER 225.34. PLEASE SEE PLANS INDICATE
 ONE MAIN UPSTAIRS AND ONE DOWNSTAIRS????
 PLEASE SEE ORIG PLANS CALLED FOR ONE
 PANEL, (EXIST)
 IT IS THIS OFFICE'S HOPE THIS IS NOT
 INSTALLED THIS WAY.
 PLEASE ALSO SEE THE EFFECT THIS WOULD
 AHVE FOR LOCATION OF GROUNDING THE
 SYSTEM AT THE MAIN HOUSE FOR THE NEW
 MAINS WHICH WILL BE REQUIRED. 250.32
  
 6) NOTE: PLEASE SEE MIN OCP FORAHU'S
 TO BE 125%. 424.3B, PLEASE SEE 50A OCP
 FOR 10KW UNIT.
  
 7) NOTE: PLEASE SEE MIN VA FOR LAUNDRY /
 WASHER CIRCUIT. 210.11C2, 220.16B
 1.5MIN
  
 8) NOTE: PLEASE SEE 100A BRKR IS BEING
 SHOWN FOR NEW ELECTRIC TANKLESS UNIT,
 HOWEVER THE LOAD IS SHOWN AS 1.2VA PER
 PHASE AND IS NOT SHOWN IN LOAD CALCS.
 THIS WILL GREATLY AFFECT LOAD CALCS.
 215.5, 220
  
 9) NOTE: PLEASE SEE REDLINED PLANS FOR
 LOAD CALCULATIONS FROM PREVIOUS PLANS
 PER 220.31B
  
 10) NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52 , SOME OF THESE WERE REMOVED FROM
 PREVIOUS PLANS AND SOME WHICH WERE
 REDLINED FROM ORIG PLANS ARE STILL NOT
 IMPLEMENTED INTO PLANS.
  
 11) NOTE: PLEASE SEE MANY AREAS/ROOMS
 WHERE THE REQUIRED EGRESS LT FIXTURE IS
 KNOW ONLY SHOWN AS A "J-BOX" , PLEASE
 KNOW, A MIN FIXTURE OF SOME SORT WILL BE
 REQUIRED FOR MIN EGRESS. 210.70,
 NFPA-101 7.8
 PLEASE REVISE PLANS.
  
 12) NOTE: PLEASE VERIFY THE MAINS AND
 SPACES AT THE 400A METER/MAIN. PLEASE
 KNOW, NO MORE THAN 6 MAINS ARE
 PERMITTED, PLEASE ALSO SEE NO MORE THAN
 5 SPACES WOULD BE PERMITTED IN
 METER/MAIN. PLEASE PROVIDE SCHEDULE FOR
 M/M OR PROVIDE INFORMATION IS INDEED
 THERE IS A 400A MAIN BRKR.
 230.70, 230.71
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  