| 2005-09-03 00:00:00 | ** REDLINED NOTES, PLAN OK AND STAMPED** | | | | | | | | | | | | PLEASE SEE 220.31B FOR LOAD | | | CALCULATIONS, | | | 1ST 8KW AT 100% | | | REMAINDER @ 40%,. 35% SHOW. | | | | | | PLEASE SEE LOAD CALCS INDICATE SERVICE | | | AT 300A'S. PLEASE SEE 310.15B6, FOR | | | 350MCM, IS RATED FOR 350A'S. SF | | | DWELLING. | | | | | | 110.26 FOR A/C DISC. | | | 210.52 FOR MASTER BEDRM RECEPT MISSING | | | WITHIN 6' OF DOOR. | | | *************************************** | | | NO CORRECTIONS NEEDED AT THIS TIME> IF | | | PLANS COME ABCK IN FOR REVISIONS DURING | | | BLDG, PLEASE MAKE ABOVE ADUSTMENTS AT | | | THAT TIME. | | | *************************************** |
|