Plan Review Notes
Plan Review Notes For Permit 04121827
Permit Number 04121827
Review Stop E
Sequence Number 4
Notes
Date Text
2005-09-03 00:00:00** REDLINED NOTES, PLAN OK AND STAMPED**
  
  
  
 PLEASE SEE 220.31B FOR LOAD
 CALCULATIONS,
 1ST 8KW AT 100%
 REMAINDER @ 40%,. 35% SHOW.
  
 PLEASE SEE LOAD CALCS INDICATE SERVICE
 AT 300A'S. PLEASE SEE 310.15B6, FOR
 350MCM, IS RATED FOR 350A'S. SF
 DWELLING.
  
 110.26 FOR A/C DISC.
 210.52 FOR MASTER BEDRM RECEPT MISSING
 WITHIN 6' OF DOOR.
 ***************************************
 NO CORRECTIONS NEEDED AT THIS TIME> IF
 PLANS COME ABCK IN FOR REVISIONS DURING
 BLDG, PLEASE MAKE ABOVE ADUSTMENTS AT
 THAT TIME.
 ***************************************