| Date |
Text |
| 2005-08-01 00:00:00 | ************ UNSAT 3RD REVIEW ********* |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS TWO |
| | REVIEWS STILL NEED TO BE ADDRESSED. |
| | PLEASE SEENEW NOTES DUE TO CHANGES IN |
| | PLANS. |
| | |
| | 1)NOTE: PLEASE SHOW ALL SERVICE |
| | EQUIPMENT ON PLANS. PLEASE SEE PREVIOUS |
| | PLANS SHOWED TWO PANELS, NOW ONE PANEL |
| | "K" HAS BEEN REMOVED AND METER/MAINS, |
| | ETC ARE NOT SHOWN? |
| | PLEASE SEE RISER NOW SHOWS PANEL "H" AS |
| | EXISTING? HOW IS THIS POSSIBLE IF THIS |
| | PANEL IS BEING SHOWN BEING LOCATED IN |
| | NEW ADDTION SECTION OF HOUSE? |
| | IF SERVICE IS LOCATED AT A DEATCHED BLDG |
| | AS NOW SHOWN ON RISER DIAGRAM, THEN |
| | PLEASE SEE 250.32 FOR GROUNDING |
| | ELECTRODE SYSTEM ETC AT DETACHED BLDG'S. |
| | PLEASE ALSO SEE NEW COMMENTS BASED ON A |
| | RISER DIAGRAM NOW BEING SUBMITTED. |
| | |
| | 2)NOTE: PLEASE SEE RISER NOW SUBMITTED, |
| | HOWEVER PLEASE SEE THAT PANEL SCHEDULES |
| | WHICH WERE SUBMITTED FOR THE LAST TWO |
| | REVIEWS HAVE NOW BEEN REMOVED FROM |
| | PLANS? |
| | PREVIOUS PLANS CALLED FOR A 400A |
| | SERVICE, PLANS NOW INDICATE A 300A |
| | SERVICE. PREVIOUS COMMENT REQUIRING A |
| | 1/0 MIN FOR GROUNDING ELECTRODE IS NO |
| | LONGER RELEVENT. |
| | PLEASE SUBMIT. UNABLE TO VERIFY SOME |
| | PREVIOUS NOTES. |
| | NEED TO VERIFY OVER CURRENT PROTECTION, |
| | CONDUCTOR SIZES, ARC FAULT PROTECTION, |
| | ETC.215.5 |
| | |
| | 3)NOTE: PLEASE SEE NEW RISER SHOWS AN |
| | EQUIPMENT GROUNDING CONDUCTOR FROM |
| | GUTTER TO GARAGE MAIN. PLEASE SEE 250.6, |
| | 250.24, "EQUIPMENT GROUNDING" CONDUCTORS |
| | ARE ONLY INSTALLED AFTER THE FIRST MEANS |
| | OF DISCONNECT. |
| | |
| | 4)NOTE: PLEASE SEE "NEW FOOTER" STEEL IS |
| | STILL NOT SHOWN TO BE A PART OF THE |
| | GROUNDING ELECTRODE SYSTEM. 250.50 |
| | |
| | 5)NOTE: PLEASE SEE BOTTOM OF LOAD |
| | CALCULATIONS STILL SHOW "EXISTING |
| | SERVICE" 200A'S.?? PLEASE SEE RISER |
| | SHOWS SERVICE AS 300A'S. |
| | PLEASE SEE LOAD FOR "GARAGE PANEL" CAN |
| | NOT BE VERIFIED AS NO PANEL SCHEDULE(S) |
| | OR IDENTIFICATION IS SHOWN. |
| | 215.5 |
| | |
| | 6)NOTE: PLEASE SEE PREVIOUS PLANS SHOWED |
| | ALL CIRCUITING, HOWEVER PLANS DO NOT |
| | SHOW THIS NOW? |
| | 215.5 |
| | |
| | 7)NOTE: PLEASE SEE PREVIOUS NOTES |
| | REFERENCED ARC FAULT PROTECTION FOR SD'S |
| | ALSO, HOWEVER "RESPONSE LTR" MENTIONS, |
| | "WHERE APPLICABLE" ?? |
| | PLEASE KNOW, SD'S ARE ALL WIRED IN-LINE |
| | AS REQUIRED IN NFPA-72 8-1.4 .ALL SD'S |
| | SHALL BE ON AN ARC FAULT PROTECTED |
| | CIRCUIT. |
| | |
| | 8)NOTE: PLEASE SEE FS 553.80(2)B) |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO A |
| | MIN OF TWO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. ONE COPY OF OLD/VOIDED SHEETS |
| | SHALL BE SUBMITTED FOR REFERENCE. |
| | ONE COPY OF ELECTRICAL PLANS HAVE BEEN |
| | RETAINED FOR FILE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | |
| | |
| | 250.50 |