Plan Review Notes
Plan Review Notes For Permit 04121827
Permit Number 04121827
Review Stop E
Sequence Number 3
Notes
Date Text
2005-08-01 00:00:00************ UNSAT 3RD REVIEW *********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS TWO
 REVIEWS STILL NEED TO BE ADDRESSED.
 PLEASE SEENEW NOTES DUE TO CHANGES IN
 PLANS.
  
 1)NOTE: PLEASE SHOW ALL SERVICE
 EQUIPMENT ON PLANS. PLEASE SEE PREVIOUS
 PLANS SHOWED TWO PANELS, NOW ONE PANEL
 "K" HAS BEEN REMOVED AND METER/MAINS,
 ETC ARE NOT SHOWN?
 PLEASE SEE RISER NOW SHOWS PANEL "H" AS
 EXISTING? HOW IS THIS POSSIBLE IF THIS
 PANEL IS BEING SHOWN BEING LOCATED IN
 NEW ADDTION SECTION OF HOUSE?
 IF SERVICE IS LOCATED AT A DEATCHED BLDG
 AS NOW SHOWN ON RISER DIAGRAM, THEN
 PLEASE SEE 250.32 FOR GROUNDING
 ELECTRODE SYSTEM ETC AT DETACHED BLDG'S.
 PLEASE ALSO SEE NEW COMMENTS BASED ON A
 RISER DIAGRAM NOW BEING SUBMITTED.
  
 2)NOTE: PLEASE SEE RISER NOW SUBMITTED,
 HOWEVER PLEASE SEE THAT PANEL SCHEDULES
 WHICH WERE SUBMITTED FOR THE LAST TWO
 REVIEWS HAVE NOW BEEN REMOVED FROM
 PLANS?
 PREVIOUS PLANS CALLED FOR A 400A
 SERVICE, PLANS NOW INDICATE A 300A
 SERVICE. PREVIOUS COMMENT REQUIRING A
 1/0 MIN FOR GROUNDING ELECTRODE IS NO
 LONGER RELEVENT.
 PLEASE SUBMIT. UNABLE TO VERIFY SOME
 PREVIOUS NOTES.
 NEED TO VERIFY OVER CURRENT PROTECTION,
 CONDUCTOR SIZES, ARC FAULT PROTECTION,
 ETC.215.5
  
 3)NOTE: PLEASE SEE NEW RISER SHOWS AN
 EQUIPMENT GROUNDING CONDUCTOR FROM
 GUTTER TO GARAGE MAIN. PLEASE SEE 250.6,
 250.24, "EQUIPMENT GROUNDING" CONDUCTORS
 ARE ONLY INSTALLED AFTER THE FIRST MEANS
 OF DISCONNECT.
  
 4)NOTE: PLEASE SEE "NEW FOOTER" STEEL IS
 STILL NOT SHOWN TO BE A PART OF THE
 GROUNDING ELECTRODE SYSTEM. 250.50
  
 5)NOTE: PLEASE SEE BOTTOM OF LOAD
 CALCULATIONS STILL SHOW "EXISTING
 SERVICE" 200A'S.?? PLEASE SEE RISER
 SHOWS SERVICE AS 300A'S.
 PLEASE SEE LOAD FOR "GARAGE PANEL" CAN
 NOT BE VERIFIED AS NO PANEL SCHEDULE(S)
 OR IDENTIFICATION IS SHOWN.
 215.5
  
 6)NOTE: PLEASE SEE PREVIOUS PLANS SHOWED
 ALL CIRCUITING, HOWEVER PLANS DO NOT
 SHOW THIS NOW?
 215.5
  
 7)NOTE: PLEASE SEE PREVIOUS NOTES
 REFERENCED ARC FAULT PROTECTION FOR SD'S
 ALSO, HOWEVER "RESPONSE LTR" MENTIONS,
 "WHERE APPLICABLE" ??
 PLEASE KNOW, SD'S ARE ALL WIRED IN-LINE
 AS REQUIRED IN NFPA-72 8-1.4 .ALL SD'S
 SHALL BE ON AN ARC FAULT PROTECTED
 CIRCUIT.
  
 8)NOTE: PLEASE SEE FS 553.80(2)B)
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO A
 MIN OF TWO COMPLETE SETS FOR REVIEW AND
 STAMPING. ONE COPY OF OLD/VOIDED SHEETS
 SHALL BE SUBMITTED FOR REFERENCE.
 ONE COPY OF ELECTRICAL PLANS HAVE BEEN
 RETAINED FOR FILE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
  
  