| 2005-06-20 00:00:00 | ******* UNSAT 2ND REVIEW ***** |
| | |
| | PLEASE SEE SOME NOTES FROM |
| | PREVIOUS/FIRST REVIEW STILL NEED TO BE |
| | ADDRESSED. |
| | |
| | 1)NOTE: NOTE#1 OK. |
| | |
| | 2)NOTE: NOTE #2, NO, NO RISER SUBMITTED |
| | ON E-1 |
| | |
| | 3)NOTE: NOTE #3 NO, NO RISER. |
| | |
| | 4)NOTE: NOTE #4 NO, NO RISER, ALTHOUGH |
| | A-SHEET APPEARS TO SHOW SERVICE GROUPED? |
| | |
| | 5)NOTE: NOTE #5 NO, NO RISER. |
| | |
| | 6)NOTE: NOTE #6 NO, NO RISER. |
| | |
| | 7)NOTE: NOTE #7 NO, NO RISER. |
| | |
| | 8)NOTE: NOTE# 8 OK, HOWEVER PLEASE SEE |
| | ONE AHU IS SHOWN WITH NO INFORMATION ON |
| | PANEL SCHEDULE? "BLANK". |
| | |
| | 9)NOTE: NOTE #9 NO, NO RISER. |
| | |
| | 10)NOTE: NOTE #10 OK. |
| | |
| | 11)NOTE: NOTE #11 OK. |
| | |
| | 12)NOTE: NOTE #12 OK. |
| | |
| | 13)NOTE: NOTE #13 NO, PLEASE SEE SOME |
| | MISSING. BATH GFI. |
| | |
| | 14)NOTE: NOTE #14 OK, HOWEVER PLEASE SEE |
| | 210.12 2002 NEC FOR ARC FAULT |
| | PROTECTION. |
| | |
| | 15)NOTE: NOTE #15 NO, NO RISER. |
| | |
| | 16)NOTE: NOTE #16 NO, PLEASE SEE |
| | 220.31B |
| | |
| | 17)NOTE: NOTE #17 NO,PLEASE SEE FIRST |
| | FLR. |
| | |
| | 18)NOTE: NOTE #18 NO, PLEASE SEE SD'S |
| | AND NOTE ABOVE. |
| | |
| | 19)NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B) ATTACHED WITH RESPECT TO |
| | DESIGN PROFESSIONAL. THIS IS ONLY A |
| | NOTICE GIVEN AT THIS TIME. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF ELECTRICAL IS BEING RETAINED |
| | FOR FILE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |