Plan Review Notes
Plan Review Notes For Permit 04121827
Permit Number 04121827
Review Stop E
Sequence Number 2
Notes
Date Text
2005-06-20 00:00:00******* UNSAT 2ND REVIEW *****
  
 PLEASE SEE SOME NOTES FROM
 PREVIOUS/FIRST REVIEW STILL NEED TO BE
 ADDRESSED.
  
 1)NOTE: NOTE#1 OK.
  
 2)NOTE: NOTE #2, NO, NO RISER SUBMITTED
 ON E-1
  
 3)NOTE: NOTE #3 NO, NO RISER.
  
 4)NOTE: NOTE #4 NO, NO RISER, ALTHOUGH
 A-SHEET APPEARS TO SHOW SERVICE GROUPED?
  
 5)NOTE: NOTE #5 NO, NO RISER.
  
 6)NOTE: NOTE #6 NO, NO RISER.
  
 7)NOTE: NOTE #7 NO, NO RISER.
  
 8)NOTE: NOTE# 8 OK, HOWEVER PLEASE SEE
 ONE AHU IS SHOWN WITH NO INFORMATION ON
 PANEL SCHEDULE? "BLANK".
  
 9)NOTE: NOTE #9 NO, NO RISER.
  
 10)NOTE: NOTE #10 OK.
  
 11)NOTE: NOTE #11 OK.
  
 12)NOTE: NOTE #12 OK.
  
 13)NOTE: NOTE #13 NO, PLEASE SEE SOME
 MISSING. BATH GFI.
  
 14)NOTE: NOTE #14 OK, HOWEVER PLEASE SEE
 210.12 2002 NEC FOR ARC FAULT
 PROTECTION.
  
 15)NOTE: NOTE #15 NO, NO RISER.
  
 16)NOTE: NOTE #16 NO, PLEASE SEE
 220.31B
  
 17)NOTE: NOTE #17 NO,PLEASE SEE FIRST
 FLR.
  
 18)NOTE: NOTE #18 NO, PLEASE SEE SD'S
 AND NOTE ABOVE.
  
 19)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) ATTACHED WITH RESPECT TO
 DESIGN PROFESSIONAL. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF ELECTRICAL IS BEING RETAINED
 FOR FILE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  