Plan Review Notes
Plan Review Notes For Permit 04121827
Permit Number 04121827
Review Stop E
Sequence Number 1
Notes
Date Text
2005-01-12 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE SHOW LOCATION OF ALL
 SERVICE EQUIPMENT ON PLANS INCLUDING
 PANELS AND IDENTIFY PANELS. 215.5
  
 2)NOTE: PLEASE SEE 310.15B6 FOR MIN
 SEC'S FOR A 400A SERVICE. 240.4B
 MIN 400MCM.
  
 3)NOTE: PLEASE SEE #4'S SHOWN FROM
 GUTTER TO 200A METERS.? PLEASE SEE
 310.15B6, #4 IS RATED FOR 100A'S ONLY.
  
 4)NOTE: PLEASE SEE 230.72 FOR GROUPING
 OF MAINS REQUIRED.
  
 5)NOTE: PLEASE SEE ONE OF THE 200A
 METER
 CANS DO NOT INDICATE WHERE THIS IS
 FEEDING?? 215.5
  
 6)NOTE: PLEASE SEE 250.6,250.24 AND
 EQUIPMENT GROUNDING CONDUCTOR IS ONLY
 INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 7)NOTE: PLEASE CORRELATE RISER DIAGRAM
 WITH PANELS. RISER INDICATES 60A SUB
 PANEL AS MLO AND PANEL IS SHOWN AS MCB.
 PLEASE ALSO SEE PANEL H SHOWS A 2P20A
 FEED TO 60A SUB PANEL.
 PLEASE ALSO SEE OCP FROM PANEL "H" TO
 PANEL K, SHOWN AS 2P20A 1KW LOAD.
  
 8)NOTE: PLEASE SEE 424.3B FIR MIN OCP
 FOR AHU'S. PLEASE SEE THESE ARE SHOWN
 AS
 2P20A W/ 1KW LOAD??
  
 9)NOTE: PLEASE SEE NEW FOOTER STEEL
 REQUIRED TO BE PART OF THE GROUNDING
 ELECTRODE SYSTEM. 250.50
  
 10)NOTE: PLEASE SEE CIRCUITING FOR BATH
 GFI'S THESE ARE TO BE 20A, #12 PER
 210.11C3.
 PLEASE SEE SOME SHOWN AS 15A ETC.
  
 11)NOTE: PLEASE SEE 210.52C1 FOR
 KITCHEN
 COUNTERSPACE.
  
 12)NOTE: PLEASE SEE 210.8A6, ALL
 KITCHEN
 COUNTERSPACE RECEPTS TO BE SHOWN AS
 GFI.
  
 13)NOTE: PLEASE SEE FBC CHAPTER 34 FOR
 ADDITIONS AND REMODELS TO EXISTING
 DWELLINGS.
 SD'S AND GFI'S TO BE BROUGHT UP TO
 CODE.
 PLEASE SHOW ALL NEW AND ANY EXISTING
 WHICH MEET CURRENT CODE.
  
 14)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 15)NOTE: PLEASE SEE 250.66 FOR MIN GEC.
 1/0 MIN.
  
 16)NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCULATIONS.
  
 17)NOTE: PLEASE PROVIDE ROOM
 DESIGNATIONS ON PLANS.
  
 18)NOTE: PLEASE SEE ARC FAULT PROTECTION
 IS TO BE UNDER THE 2002 NEC.210.12
 AFCI PROTECTION IS FOR ALL "OUTLETS,
 SD'S LTS , FANS ETC. PLEASE SEE
 CIRCUITING.
  
 PLEASE SEE MANY OF THESE ITEMS HAVE
 BEEN REDLINED ON ONE SET OF PLANS FOR
 AREAS OF NOTES.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS SHOWULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]