| 2005-01-12 00:00:00 | ************ UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SHOW LOCATION OF ALL |
| | SERVICE EQUIPMENT ON PLANS INCLUDING |
| | PANELS AND IDENTIFY PANELS. 215.5 |
| | |
| | 2)NOTE: PLEASE SEE 310.15B6 FOR MIN |
| | SEC'S FOR A 400A SERVICE. 240.4B |
| | MIN 400MCM. |
| | |
| | 3)NOTE: PLEASE SEE #4'S SHOWN FROM |
| | GUTTER TO 200A METERS.? PLEASE SEE |
| | 310.15B6, #4 IS RATED FOR 100A'S ONLY. |
| | |
| | 4)NOTE: PLEASE SEE 230.72 FOR GROUPING |
| | OF MAINS REQUIRED. |
| | |
| | 5)NOTE: PLEASE SEE ONE OF THE 200A |
| | METER |
| | CANS DO NOT INDICATE WHERE THIS IS |
| | FEEDING?? 215.5 |
| | |
| | 6)NOTE: PLEASE SEE 250.6,250.24 AND |
| | EQUIPMENT GROUNDING CONDUCTOR IS ONLY |
| | INSTALLED AFTER THE FIRST MEANS OF |
| | DISCONNECT. |
| | |
| | 7)NOTE: PLEASE CORRELATE RISER DIAGRAM |
| | WITH PANELS. RISER INDICATES 60A SUB |
| | PANEL AS MLO AND PANEL IS SHOWN AS MCB. |
| | PLEASE ALSO SEE PANEL H SHOWS A 2P20A |
| | FEED TO 60A SUB PANEL. |
| | PLEASE ALSO SEE OCP FROM PANEL "H" TO |
| | PANEL K, SHOWN AS 2P20A 1KW LOAD. |
| | |
| | 8)NOTE: PLEASE SEE 424.3B FIR MIN OCP |
| | FOR AHU'S. PLEASE SEE THESE ARE SHOWN |
| | AS |
| | 2P20A W/ 1KW LOAD?? |
| | |
| | 9)NOTE: PLEASE SEE NEW FOOTER STEEL |
| | REQUIRED TO BE PART OF THE GROUNDING |
| | ELECTRODE SYSTEM. 250.50 |
| | |
| | 10)NOTE: PLEASE SEE CIRCUITING FOR BATH |
| | GFI'S THESE ARE TO BE 20A, #12 PER |
| | 210.11C3. |
| | PLEASE SEE SOME SHOWN AS 15A ETC. |
| | |
| | 11)NOTE: PLEASE SEE 210.52C1 FOR |
| | KITCHEN |
| | COUNTERSPACE. |
| | |
| | 12)NOTE: PLEASE SEE 210.8A6, ALL |
| | KITCHEN |
| | COUNTERSPACE RECEPTS TO BE SHOWN AS |
| | GFI. |
| | |
| | 13)NOTE: PLEASE SEE FBC CHAPTER 34 FOR |
| | ADDITIONS AND REMODELS TO EXISTING |
| | DWELLINGS. |
| | SD'S AND GFI'S TO BE BROUGHT UP TO |
| | CODE. |
| | PLEASE SHOW ALL NEW AND ANY EXISTING |
| | WHICH MEET CURRENT CODE. |
| | |
| | 14)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | |
| | 15)NOTE: PLEASE SEE 250.66 FOR MIN GEC. |
| | 1/0 MIN. |
| | |
| | 16)NOTE: PLEASE SEE 220.31B FOR LOAD |
| | CALCULATIONS. |
| | |
| | 17)NOTE: PLEASE PROVIDE ROOM |
| | DESIGNATIONS ON PLANS. |
| | |
| | 18)NOTE: PLEASE SEE ARC FAULT PROTECTION |
| | IS TO BE UNDER THE 2002 NEC.210.12 |
| | AFCI PROTECTION IS FOR ALL "OUTLETS, |
| | SD'S LTS , FANS ETC. PLEASE SEE |
| | CIRCUITING. |
| | |
| | PLEASE SEE MANY OF THESE ITEMS HAVE |
| | BEEN REDLINED ON ONE SET OF PLANS FOR |
| | AREAS OF NOTES. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO TWO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD SHEETS SHOWULD BE |
| | SUBMITTED FOR REFERENCE ONLY. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |