| 2005-01-21 00:00:00 | DENIED |
| | |
| | |
| | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT |
| | SHALL BE RECORDED AT PALM BEACH COUNTY |
| | COURTHOUSE AND A COPY SUBMITTED TO THIS |
| | OFFICE BEFORE A PERMIT CAN BE ISSUED. |
| | BLANK FORMS ARE AVAILABLE FROM THIS |
| | OFFICE. |
| | NOTE: THE NOTICE OF COMMENCEMENT MUST BE |
| | RE-RECORDED IF THE DESCRIBED IMPROVEMENT |
| | OR CONSTRUCTION IS NOT COMMENCED WITHIN |
| | 90 DAYS OF RECORDING. |
| | |
| | |
| | 2.BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 3.PRODUCT APPROVALS: |
| | PRODUCT APPROVALS ARE REQUIRED FOR THE |
| | FOLLOWING:STRAPS AND TIE-DOWNS, |
| | EXTERIOR DOORS, WINDOWS, IMPACT |
| | PROTECTION, TILE ROOF AND FLAT ROOF. |
| | ALL PRODUCT APPROVALS REQUIRE THE |
| | FOLLOWING TO BE ATTACHED. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | |
| | 4.1015.2 HEIGHT. GUARDRAILS SHALL FORM |
| | A VERTICAL PROTECTIVE BARRIER NOT LESS |
| | THAN 42" HIGH. |
| | 1015.3 OPENINGS. OPEN GUARDRAILS |
| | SHALL HAVE INTERMEDIATE RAILS OR ORNA- |
| | MENTAL PATTERNS SUCH AS A 4" DIAMETER |
| | SPHERE CAN NOT PASS THROUGH. A BOTTOM |
| | RAIL OR CURB SHALL BE PROVIDED THAT WILL |
| | REJECT THE PASSAGE OF 2" DIAMETER |
| | SPHERE.SEE ALSO A-8 #1 |
| | |
| | |
| | 5. FBC 2309.6ACCESS TO ATTIC SPACE |
| | EACH ATTIC SPACE WITH A CLEAR HEIGHT OF |
| | 24" OR GREATER SHALL BE PROVIDED WITH AN |
| | INTERIOR ATTIC ACCESS OPENING NOT LESS |
| | THAN 20"X 36".PLEASE SHOW LOCATIONS ON |
| | PLANS. |
| | |
| | 6. SHOW HANDRAILS AT STAIRS ON S-3 #1 |
| | |
| | 7.SHOW HOW EXISTING BUILDING WILL |
| | COMPLY FOR GFCI OUTLETS AND SMOKE |
| | DETECTORS. FBC 3401.7.1.2.1 |
| | |
| | 8.SUBMIT 2 COPIES OF ENERGY CALCS. |
| | |
| | 9.SHOW SIZE AND TYPE OF BEDROOM |
| | WINDOWS AND SILL HEIGHT FROM FLOOR. |
| | FBC 1005.4 |
| | |
| | 10. CHIMNEY HEIGHT SHALL COMPLY WITH |
| | FBC 2804.2.4 |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | ART LANGE |
| | BUILDING PLANS EXAMINER |
| | 805-6672 |