Plan Review Notes
Plan Review Notes For Permit 04121817
Permit Number 04121817
Review Stop E
Sequence Number 4
Notes
Date Text
2005-07-05 00:00:00********** UNSAT ************
  
  
 1)NOTE: PLEASE SEE PLANS ARE NOW COMING
 IN WITH A NEW GEN ETC BEING ADDED.
 PLEASE SEE THIS IS REQUIRED TO BE UNDER
 A SEPARATE PERMIT. PLEASE SUBMITTHE
 REVISED RISER DIAGRAM, MANUFACTURES
 SPECS FOR GEN, ATS, PANEL ETC.
 PLEASE GEN MENTIONS GAS?, HOWEVER LP PR
 NATURAL.?
 PLEASE PROVIDE LOAD CALCUALTIONS, PANEL
 SCHEDULE FOR GEN SUB PANEL AND INTENDED
 LOADS. 702.5, 225.36
 GEN LOADS MUST BE SPECIFIC AND SHALL NOT
 HAVE THE SAME DERATINGS AS GEN LTS/
 RECEPTS. PLEASE SEE ALL CONNECTED MOTOR,
 APPL LOADS ARE 100%, AND CONTINUOUS
 LOADS ARE 125%
 PLEASE ALSO SEE ZONING COMMENTS.
 215.5
  
 2)NOTE: PLEASE SHOW ALL SERVICE
 EQUIPMENT ON PLANS. DISC ETC.
 PLEASE SEE 225.34 FOR GROUPING OF MAINS.
  
 PLEASE SEE DISC FOR PANEL "H" COULD NOT
 BE LOCATED ON PLANS NEXT TO PANEL A?C
 ETC.
  
 3)NOTE: PLEASE SUBMIT REVISED PLANS FOR
 MAIN HOUSE DENOTING GEN UNDER SEPARATE
 PERMIT. PLEASE ALSO SUBMIT THIS REVISION
 AFTERGEN IS APPLIED AND ISSUED FOR
 PERMIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
2005-07-01 00:00:00IN ELECTRCIAL FOR REVIEW.
 NOTES TO FOLLOW.