| 2005-07-05 00:00:00 | ********** UNSAT ************ |
| | |
| | |
| | 1)NOTE: PLEASE SEE PLANS ARE NOW COMING |
| | IN WITH A NEW GEN ETC BEING ADDED. |
| | PLEASE SEE THIS IS REQUIRED TO BE UNDER |
| | A SEPARATE PERMIT. PLEASE SUBMITTHE |
| | REVISED RISER DIAGRAM, MANUFACTURES |
| | SPECS FOR GEN, ATS, PANEL ETC. |
| | PLEASE GEN MENTIONS GAS?, HOWEVER LP PR |
| | NATURAL.? |
| | PLEASE PROVIDE LOAD CALCUALTIONS, PANEL |
| | SCHEDULE FOR GEN SUB PANEL AND INTENDED |
| | LOADS. 702.5, 225.36 |
| | GEN LOADS MUST BE SPECIFIC AND SHALL NOT |
| | HAVE THE SAME DERATINGS AS GEN LTS/ |
| | RECEPTS. PLEASE SEE ALL CONNECTED MOTOR, |
| | APPL LOADS ARE 100%, AND CONTINUOUS |
| | LOADS ARE 125% |
| | PLEASE ALSO SEE ZONING COMMENTS. |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SHOW ALL SERVICE |
| | EQUIPMENT ON PLANS. DISC ETC. |
| | PLEASE SEE 225.34 FOR GROUPING OF MAINS. |
| | |
| | PLEASE SEE DISC FOR PANEL "H" COULD NOT |
| | BE LOCATED ON PLANS NEXT TO PANEL A?C |
| | ETC. |
| | |
| | 3)NOTE: PLEASE SUBMIT REVISED PLANS FOR |
| | MAIN HOUSE DENOTING GEN UNDER SEPARATE |
| | PERMIT. PLEASE ALSO SUBMIT THIS REVISION |
| | AFTERGEN IS APPLIED AND ISSUED FOR |
| | PERMIT. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |