| 2005-02-10 00:00:00 | *************** UNSAT 2ND REVIEW ****** |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | |
| | 1)NOTE: NOTE #1 OK |
| | |
| | 2)NOTE: NOTE #2 NO, PLEASE SEE MIN SEC'S |
| | |
| | PER 310.16/310.15B6, 240.4B. |
| | ** NOTE** IF SEC'S ARE BEING SUPPLIED BY |
| | FPL, THEN THEY DO NOT NEED TO BE SHOWN. |
| | |
| | 3)NOTE: NOTE #3 NO, PLEASE SEE 250.66 |
| | FOR SIZING OF GEC. MIN 1/0 |
| | |
| | 4)NOTE: NOTE#4 OK, SEE PREVIOUS COMMENT |
| | FOR SEC'S. |
| | |
| | 5)NOTE: NOTE#5 OK |
| | |
| | 6)NOTE: NOTE #6 OK |
| | |
| | 7)NOTE: NOTE #7 OK |
| | |
| | 8)NOTE: NOTE #8 OK, HOWEVER THERE ARE |
| | NOW TWO KITCHEN COUNTERSPACES SHOWN |
| | W/OUT ANY GFI RECEPTS REQUIRED PER |
| | 210.52C1 |
| | |
| | 9)NOTE: NOTE #9 OK |
| | |
| | 10)NOTE: NOTE #10 OK |
| | |
| | 11)NOTE: NOTE #11 OK |
| | |
| | 12)NOTE: NOTE #12 NO, SEE NOTE #8 |
| | |
| | 13)NOTE: NOTE #13 NO, PLEASE SEE COTTAGE |
| | AND CIRCUITING FOR SLEEPING AREAS PER |
| | 210.12 2002 NEC. |
| | |
| | 14)NOTE: NOTE #14 NO, PLEASE SEE COTTAGE |
| | FIRST AND SECOND FLOOR. |
| | NFPA-72 8-1.4.1.6.2 |
| | |
| | 15)NOTE: NOTE#15 NO, PLEASE SEE 220.31B |
| | FOR LOAD CALCUALTIONS. |
| | |
| | ************************************* |
| | PLEASE SEE NEW NOTE: |
| | |
| | 1)NOTE: PLEASE SEE 250.50,250.32 FOR |
| | GROUNDING ELECTRODE SYSTEM AND REQUIRED |
| | GROUNDING AT DETACHED BLDGS. |
| | PLEASE INCLUDE NEW FOOTER STEEL PER |
| | 250.50 AND DETACHED BLDG PER 250.32. |
| | |
| | 2)NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B) ATTACHED WITH RESPECT TO |
| | DESIGN PROFESSIONAL. THIS IS GIVEN AS A |
| | NOTICE ONLY. |
| | |
| | PLEASE REMOVE ALL OLD VOIDED SHEETS AND |
| | INSERT ONLY NEW SHEETS INTO TWO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. AS |
| | REQUESTED ON PREVIOUS REVIEW, PLEASE |
| | SUBMIT ONE SET OF OLD SHEETS FOR |
| | REFERENCE. OLD SET WAS NOT RESUBMITTED |
| | FOR REFERENCE WITH THIS RESUB. |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |