| Date |
Text |
| 2006-06-25 00:00:00 | ********** UNSAT ********* |
| | |
| | |
| | 1) NOTE: PLEASE SEE LANDSCAPE LIGHTING |
| | WAS NO PART OF ORIGINAL PLANS AND SHALL |
| | BE SUBMITTED UNDER A NEW PERMIT AND NEW |
| | PERMIT APPLICATION. |
| | FBC 105.1 ADMIN SECT. |
| | 106.1.2 |
| | |
| | 2) NOTE: PLEASE SEE PANEL STP IS SHOWING |
| | WRONG CONDUCTOR SIZES. THE OCP AND AWG |
| | WAS REDLINED ON THREE SETS OF PREVIOUS |
| | PLANS AND MUST BE CORRECTED. |
| | PLEASE ALSO SEE CU LOAD IS SHOWN AS |
| | 10.4KW, YET THE OCP IS ONLY 30A'S?? |
| | PLEASE REVISE AND ADJUST. |
| | 240.4,310.16, 424.3B, ETC |
| | |
| | 3) NOTE: PLEASE SEE PANEL SCHEDULES ARE |
| | NOW MISSING ALL REQUIRED KVA INDICATIONS |
| | FOR APPLIANCES/MOTOR/ AND A/C LOADS. |
| | CAN NOT VERIFY OCP AND CORRECT CONDUCTOR |
| | SIZES AT THIS TIME. |
| | PLEASE COMPLETE. |
| | 408.4,310.16,240.4, 215.5 |
| | |
| | 4) NOTE: PLEASE SEE PANEL SCHEDULE SHALL |
| | INCLUDE ALL CIRCUITS SPECIFIC TO AREAS |
| | AND ROOMS IN WHICH THEY FEED. GEN |
| | LTS/GEN RECEPTS IS NO ACCEPTABLE FOR |
| | FINAL. |
| | IE; BEDRM #3 RECEPTS, FAMILY RM LTS, |
| | KITCHEN LTS, ETC |
| | ALL ROOMS AND AREAS SHALL CONTAIN |
| | DESIGNATIONS TO CORRELATE WITH PANEL |
| | SCHEDULE. |
| | 408.4, 215.5, 106.1.2 |
| | |
| | 5) NOTE: PLEASE SEE WATER HEATER IS |
| | SHOWING 310AWG, WITH A 2-POLE 20? |
| | PLEASE VERIFY OCP AN AWG. |
| | 240.4,310.16, |
| | |
| | 6) NOTE: PLEASE VERIFY MANY CIRCUITS ARE |
| | SHOWING #12 AWG WITH 15A OCP? THIS IS |
| | OK, HOWEVER IF SHOWN THIS WAY , THIS IS |
| | WHAT WILL BE REQUIRED TO BE INSTALLED. |
| | 215.5 |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |