2006-06-25 00:00:00********** UNSAT *********
  
  
 1) NOTE: PLEASE SEE LANDSCAPE LIGHTING
 WAS NO PART OF ORIGINAL PLANS AND SHALL
 BE SUBMITTED UNDER A NEW PERMIT AND NEW
 PERMIT APPLICATION.
 FBC 105.1 ADMIN SECT.
 106.1.2
  
 2) NOTE: PLEASE SEE PANEL STP IS SHOWING
 WRONG CONDUCTOR SIZES. THE OCP AND AWG
 WAS REDLINED ON THREE SETS OF PREVIOUS
 PLANS AND MUST BE CORRECTED.
 PLEASE ALSO SEE CU LOAD IS SHOWN AS
 10.4KW, YET THE OCP IS ONLY 30A'S??
 PLEASE REVISE AND ADJUST.
 240.4,310.16, 424.3B, ETC
  
 3) NOTE: PLEASE SEE PANEL SCHEDULES ARE
 NOW MISSING ALL REQUIRED KVA INDICATIONS
 FOR APPLIANCES/MOTOR/ AND A/C LOADS.
 CAN NOT VERIFY OCP AND CORRECT CONDUCTOR
 SIZES AT THIS TIME.
 PLEASE COMPLETE.
 408.4,310.16,240.4, 215.5
  
 4) NOTE: PLEASE SEE PANEL SCHEDULE SHALL
 INCLUDE ALL CIRCUITS SPECIFIC TO AREAS
 AND ROOMS IN WHICH THEY FEED. GEN
 LTS/GEN RECEPTS IS NO ACCEPTABLE FOR
 FINAL.
 IE; BEDRM #3 RECEPTS, FAMILY RM LTS,
 KITCHEN LTS, ETC
 ALL ROOMS AND AREAS SHALL CONTAIN
 DESIGNATIONS TO CORRELATE WITH PANEL
 SCHEDULE.
 408.4, 215.5, 106.1.2
  
 5) NOTE: PLEASE SEE WATER HEATER IS
 SHOWING 310AWG, WITH A 2-POLE 20?
 PLEASE VERIFY OCP AN AWG.
 240.4,310.16,
  
 6) NOTE: PLEASE VERIFY MANY CIRCUITS ARE
 SHOWING #12 AWG WITH 15A OCP? THIS IS
 OK, HOWEVER IF SHOWN THIS WAY , THIS IS
 WHAT WILL BE REQUIRED TO BE INSTALLED.
 215.5
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  