Plan Review Notes
Plan Review Notes For Permit 04121817
Permit Number 04121817
Review Stop P
Sequence Number 1
Notes
Date Text
2005-01-15 00:00:00DENIED;
 1.P.1 DISHWASHERS TO TIE INDIRECT INTO
 KITCHEN SINK.
 2.OUTSIDE SHOWER NOT PERMITED TO HAVE A
 DRAIN TO SANITARY SEWER. RAIN WATER NOT
 TO DISCHARGE INTO SEWER SYSTEM.
 3.MASTER BATHROOM RISER DIAGRAM, SHOWER
 NOT VENTED. SEE RED LINES.
 4.SANITARY RISER # 2 SHOWER NOT VENTED
 SEE RED LINE.
 5.FIRST FLOOR RISER DIAGRAM. W/M DRAIN
 REQUIRES A VENT.
 6.TWO WAY C.O. REQUIRED 3' OUTSIDE OF
 HOUSE AND OUTSIDE GUEST HOUSE.
 PLUMBING PLAN REVIEW BY;