| Notes |
| Date |
Text |
| 2005-01-15 00:00:00 | DENIED; | | | 1.P.1 DISHWASHERS TO TIE INDIRECT INTO | | | KITCHEN SINK. | | | 2.OUTSIDE SHOWER NOT PERMITED TO HAVE A | | | DRAIN TO SANITARY SEWER. RAIN WATER NOT | | | TO DISCHARGE INTO SEWER SYSTEM. | | | 3.MASTER BATHROOM RISER DIAGRAM, SHOWER | | | NOT VENTED. SEE RED LINES. | | | 4.SANITARY RISER # 2 SHOWER NOT VENTED | | | SEE RED LINE. | | | 5.FIRST FLOOR RISER DIAGRAM. W/M DRAIN | | | REQUIRES A VENT. | | | 6.TWO WAY C.O. REQUIRED 3' OUTSIDE OF | | | HOUSE AND OUTSIDE GUEST HOUSE. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|