Plan Review Notes
Plan Review Notes For Permit 04121817
Permit Number 04121817
Review Stop E
Sequence Number 1
Notes
Date Text
2005-01-12 00:00:00************* UNSAT *******************
 ***************************************
  
 PLEASE SEE FBC CHAPTER 34 FOR REMODEL OF
 EXISTING DWELLINGS AND ALL REQUIRED TO
 BE BROUGHT UP TO CODE.
 ***************************************
 ***************************************
  
 PLEASE SEE PLANS ARE REDLINED WITH AREAS
 OF CONCERN AS NOTED BELOW.
  
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 WITH PANELS. MCB ? MLO? PANEL "C".
  
 2)NOTE: PLEASE SEE 310.15B6 FOR MIN
 SEC'S. 400 MCM FOR 400A SERVICE.
 240.4
  
 3)NOTE: PLEASE SEE 250.66 FOR SIZING OF
 GEC. MIN 1/0.
 BASED ON 310.15B6
  
 4)NOTE: PLEASE SEE 400A METER CAN DOES
 NOT INDICATE A SECOND 200A MCB TO FEED
 TWO 200A PANELS?
 PLEASE ALSO VERIFY METER SHOWN WITH
 3/0'S??
  
 5)NOTE: PLEASE SEE 110.26 FIR MIN
 CLEARENCE FOR DISC FOR A/C UNITS.
  
 6)NOTE: PLEASE SEE 210.63 FOR MISSING
 GFI FOR COND UNITS.
  
 7)NOTE: PLEASE SEE 210.70 FOR MISSING
 CONTROL OF EGRESS LIGHTING. SEE REDLINES
 FOR LOCATIONS.
  
 8)NOTE: PLEASE SEE 210.8A6 FOR ALL
 RECEPTS SERVING KITCHEN COUNTERSPACE TO
 BE SHOWN AS GFI.
  
 9)NOTE: PLEASE ALSO SEE ALL OTHERS
 REQUIRED TO BE GFI PER 210.8, GARAGE,
 OUTSIDE, BATHS ETC.
  
 10)NOTE: PLEASE SEE MISSING FRONT AND
 REAR RECEPTS PER 210.52E
  
 11)NOTE: PLEASE SEE MANY ITEMS ON PANEL
 SCHEDULE WHICH OCP DOES NOT MEET AWG OR
 VICE/VERSA.
 PLEASE SEE 1-POLE 30A BRKRS FOR 2-POLE
 CIRCUITS, RANGE ON 1-P20A AND 1-P30A ETC
 ETC.
 REDLINED:
  
 12)NOTE: PLEASE SEE 210.52C1 FOR RECEPT
 SPACING ALONG KITCHEN COUNTERSPACE.
  
 13)NOTE: PLEASE SEE WE ARE UNDER THE
 2002 NEC FOR 210.12 AND ARC FAULT
 PROTECTION. PLEASE SEE CIRCUITING AND
 ALL "OUTLETS" REQUIRED TO BE ARC-FAULT
 PROTECTED.
  
 14)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 15)NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCULATIONS.
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 *** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHOULD BE SUBMITTED FOR
 REFERENCE ONLY.
  
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]