| 2005-01-12 00:00:00 | ************* UNSAT ******************* |
| | *************************************** |
| | |
| | PLEASE SEE FBC CHAPTER 34 FOR REMODEL OF |
| | EXISTING DWELLINGS AND ALL REQUIRED TO |
| | BE BROUGHT UP TO CODE. |
| | *************************************** |
| | *************************************** |
| | |
| | PLEASE SEE PLANS ARE REDLINED WITH AREAS |
| | OF CONCERN AS NOTED BELOW. |
| | |
| | |
| | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM |
| | WITH PANELS. MCB ? MLO? PANEL "C". |
| | |
| | 2)NOTE: PLEASE SEE 310.15B6 FOR MIN |
| | SEC'S. 400 MCM FOR 400A SERVICE. |
| | 240.4 |
| | |
| | 3)NOTE: PLEASE SEE 250.66 FOR SIZING OF |
| | GEC. MIN 1/0. |
| | BASED ON 310.15B6 |
| | |
| | 4)NOTE: PLEASE SEE 400A METER CAN DOES |
| | NOT INDICATE A SECOND 200A MCB TO FEED |
| | TWO 200A PANELS? |
| | PLEASE ALSO VERIFY METER SHOWN WITH |
| | 3/0'S?? |
| | |
| | 5)NOTE: PLEASE SEE 110.26 FIR MIN |
| | CLEARENCE FOR DISC FOR A/C UNITS. |
| | |
| | 6)NOTE: PLEASE SEE 210.63 FOR MISSING |
| | GFI FOR COND UNITS. |
| | |
| | 7)NOTE: PLEASE SEE 210.70 FOR MISSING |
| | CONTROL OF EGRESS LIGHTING. SEE REDLINES |
| | FOR LOCATIONS. |
| | |
| | 8)NOTE: PLEASE SEE 210.8A6 FOR ALL |
| | RECEPTS SERVING KITCHEN COUNTERSPACE TO |
| | BE SHOWN AS GFI. |
| | |
| | 9)NOTE: PLEASE ALSO SEE ALL OTHERS |
| | REQUIRED TO BE GFI PER 210.8, GARAGE, |
| | OUTSIDE, BATHS ETC. |
| | |
| | 10)NOTE: PLEASE SEE MISSING FRONT AND |
| | REAR RECEPTS PER 210.52E |
| | |
| | 11)NOTE: PLEASE SEE MANY ITEMS ON PANEL |
| | SCHEDULE WHICH OCP DOES NOT MEET AWG OR |
| | VICE/VERSA. |
| | PLEASE SEE 1-POLE 30A BRKRS FOR 2-POLE |
| | CIRCUITS, RANGE ON 1-P20A AND 1-P30A ETC |
| | ETC. |
| | REDLINED: |
| | |
| | 12)NOTE: PLEASE SEE 210.52C1 FOR RECEPT |
| | SPACING ALONG KITCHEN COUNTERSPACE. |
| | |
| | 13)NOTE: PLEASE SEE WE ARE UNDER THE |
| | 2002 NEC FOR 210.12 AND ARC FAULT |
| | PROTECTION. PLEASE SEE CIRCUITING AND |
| | ALL "OUTLETS" REQUIRED TO BE ARC-FAULT |
| | PROTECTED. |
| | |
| | 14)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | |
| | 15)NOTE: PLEASE SEE 220.31B FOR LOAD |
| | CALCULATIONS. |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY HAVE AN AFFECT ON |
| | ELECTRICAL PLANS. |
| | |
| | *** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD SHOULD BE SUBMITTED FOR |
| | REFERENCE ONLY. |
| | |
| | |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |