Plan Review Notes
Plan Review Notes For Permit 04121817
Permit Number 04121817
Review Stop B
Sequence Number 1
Notes
Date Text
2005-01-24 00:00:00DENIED
  
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.PLEASE SIGN OWNER/AGENT ON ENERGY
 CALCS.
  
 3.EXISTING BUILDING SHALL COMPLY WITH
  
 FBC 3401.7.2.6WHEN REPAIR AND
 ALTERATIONS AMOUNTING TO MORE THAN 50%
 OF THE VALUE OF THE EXISTING BUILDING
 ARE MADE DURING ANY 12 MONTH PERIOD,
 THE
 BUILDINGSHALL BE MADE TO CONFORM TO
 THE REQUIREMENTS OF A NEW BUILDING.
 SHOW HOW THIS WILL BE COMPLETED.
  
 4.BUILDING IS IN A FLOOD ZONE.SUBMIT
 2 COPIES OF AN ELEVATION CERTIFICATE
 SHOWING BASE FLOOD ELAVATION AND FINISH
 FLOOR HEIGHT.ALSO SHOW HOW BUILDING
 WILL COMPLY WITH SEC 94546 OF THE WPB
 MUNI-CODE
  
 5.SUBMIT TWO COPIES OF SOILS REPORT.
  
 6.PRODUCT APPROVALS:
 A.DESIGNER DOORS MISSING DCA STATE
 APPROVAL.
 B.THE FOLLOWING ARE MISSING PRODUCT
 APPROVAL WITH QUALITY ASSURANCE, EXAMPLE
 (MIAMI-DADE).
 THERMA-TRU EXTERIOR DOORS, KOLBE AND
 KOLBE MILLWORK PRODUCTS,
 C. NO PRODUCT APPROVALS HAVE BEEN
 SUBMITTED FOR THE FOLLOWING, MULLIONS,
 SIDING, AND STRAPS AND TIE-DOWNS.
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING TO BE ATTACH TO THE QUALITY
 ASSURANCE.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 7.1015.2 HEIGHT. GUARDRAILS SHALL FORM
 A VERTICAL PROTECTIVE BARRIER NOT LESS
 THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672