| 2005-01-06 00:00:00 | |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1}THE PLAN SHOWS A METER/MAIN AND THE |
| | RISER SHOWS A PANEL AND METER SEPERATE, |
| | PLEASE CORRELATE. |
| | |
| | NOTE: USING FIVE 2-POLE BREAKERS AS |
| | "MAINS" IN A TWELVE SPACE PANEL LEAVES |
| | ROOM FOR TWO SINGLE POLE BREAKERS, NOT |
| | MEETING THE INTENT OF THE SIX MEANS OF |
| | DISCONNECT IN ARTICLE 230.70, 71 OR THE |
| | EXCEPTIONS OUTLINED IN 230.40. |
| | |
| | 2} THE DEMAND CALCULATION SHOWS A/C #1 |
| | & |
| | #2 AS 5000 WATTS, PANELSCHEDULE SHOWS |
| | 11000, AND THE LOADS ARE SHOWN AS 7150 |
| | W |
| | AFTER DEMAND . PLEASE CORRELATE. |
| | |
| | 3} NOTE: THE LOAD CALCULATION AFTER |
| | DEMAND IS 199 AMPS ON A 200 AMP SERVICE |
| | LEAVING NO ROOM FOR FUTURE ADDITIONAL |
| | LOADS. WHILE THIS SERVICE DOES MEET THE |
| | MINIMUM CRITERIA A LARGER SERVICE IS |
| | RECOMMENDED. |
| | |
| | 4} THE TERM "ARCHITECTS" IN THE TITLE |
| | BLOCK INDICATES A FIRM OR BUSINESS AND |
| | THEREFORE REQUIRES A CERTIFICATE OF |
| | AUTHORIZATION NUMBER ALSO ON THE TITLE |
| | BLOCK PER 61G1-16.004(2) FAC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |