Plan Review Notes
Plan Review Notes For Permit 04121745
Permit Number 04121745
Review Stop B
Sequence Number 1
Notes
Date Text
2005-01-13 00:00:00DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PLAN SHEETS SD1 AND SD2 DO NOT HAVE
 THE ORIGINAL WET SIGNATURE OF THE
 ENGINEER AS REQUIRED BY FAC
 61G15-23.002.
  
 3) ON SHEET RF-1 THE UPLIFT VALUE FOR
 THE USC 53 CONNECTOR INCLUDES THE ONE
 THIRD INCREASE IN THE STEEL CALCS. WHICH
 IS NOT ALLOWED BY FBC 1609.4.3. THE
 MAXIMUM UPLIFT IS 11,150# PER THE
 MANUFACTUER'S CATALOG.
  
 4) SUBMIT TWO COPIES OF PRODUCT
 APPROVALS, KEY PLANS AND INSTALLATION
 SCHEDULES FOR THE STORM PANELS OR APPLY
 UNDER A SEPARATE PERMIT.
  
 5) THE PRODUCT APPROVALS FOR THE GARAGE
 DOORS HAVE THE WRONG EVALUATION REPORTS.
 SUBMIT THE PROPER EVALUATION/TEST REPORT
 AND INSTALLATION DRAWINGS THAT ARE ON
 THE STATE PROD. APPROVAL WEBSITE.
  
 6) THE MIAMI-DADE NOA FOR THERMA-TRU
 CORPORATION SUBMITTED WITH THE STATE
 PRODUCT APPROVAL COVER SHEET FOR
 BENCHMARK APPEAR TO BE TWO DIFFERENT
 PRODUCTS. SUBMIT DOCUMENTATION THAT
 THESE ARE THE SAME COMPANY AND THE
 PRODUCTS.
  
 7) SUBMIT STATE/LOCAL PRODUCT APPROVAL
 FOR THE STRUCTURAL WINDOW MULLIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714