2005-02-08 00:00:00********* UNSAT ***********
  
 PLEASE SEE NOTES # 2 AND 4 FROM
 PREVIOUS REVIEW.
  
 1)NOTE: PLEASE SEE PLANS NEED TO
 INDICATE ALL ITEMS EITHER NEW OR
 EXISTING. SOME ELECTRICAL SHOWN BUT
 THERE IS NO INDICATION? APPL MENTIONS
 NEW CEILING FANS LTS TECYET, NOTHING
 IS SHOWN FOR ANY OF THESE. LOCATIONS OF
 BOXES, SWITCHES?
  
 2)NOTE: PLEASE SEE2002 NEC FOR MIN
 REQUIRED. 210.12 FOR ARC FAULT FOR NEW
 IN BEDRMS.
 210.70 FOR EGRESS LIGHTING, NEW ?
 EXISTING? LOCATIONS?
 210.52 FOR RECEPT SPACING TO BE BROUGHT
 UP TO CODE OR EXISTING MEETS CODE?
 PLANS DO NOT INDICATE RECEPT SPACING
 MEETING CODE.
  
 3)NOTE: **NOTE** PANEL LOCATION SHOWN
 DOES NOT MEETS 110.26, PLEASE VERIFY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  