| Plan Review Notes For Permit 04121387 |
| Permit Number |
04121387 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-02-08 00:00:00 | ********* UNSAT *********** | | | | | | PLEASE SEE NOTES # 2 AND 4 FROM | | | PREVIOUS REVIEW. | | | | | | 1)NOTE: PLEASE SEE PLANS NEED TO | | | INDICATE ALL ITEMS EITHER NEW OR | | | EXISTING. SOME ELECTRICAL SHOWN BUT | | | THERE IS NO INDICATION? APPL MENTIONS | | | NEW CEILING FANS LTS TECYET, NOTHING | | | IS SHOWN FOR ANY OF THESE. LOCATIONS OF | | | BOXES, SWITCHES? | | | | | | 2)NOTE: PLEASE SEE2002 NEC FOR MIN | | | REQUIRED. 210.12 FOR ARC FAULT FOR NEW | | | IN BEDRMS. | | | 210.70 FOR EGRESS LIGHTING, NEW ? | | | EXISTING? LOCATIONS? | | | 210.52 FOR RECEPT SPACING TO BE BROUGHT | | | UP TO CODE OR EXISTING MEETS CODE? | | | PLANS DO NOT INDICATE RECEPT SPACING | | | MEETING CODE. | | | | | | 3)NOTE: **NOTE** PANEL LOCATION SHOWN | | | DOES NOT MEETS 110.26, PLEASE VERIFY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|