Plan Review Notes For Permit 04121387
Permit Number 04121387
Review Stop E
Sequence Number 1
Notes
Date Text
2004-12-30 00:00:00**************** UNSAT ***************
  
  
 1)NOTE:SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 PLANS ONLY SHOWN ONE SD?
  
 2)NOTE: PLEASE SEE 210.52 FOR MIN RECEPT
 SPACING. PLANS SHOWS MANY WALLS TO BE
 DRYWALLED W/OUT NAY VERIFICATION ON
 WHEATHER RECEPTS ARE EXISITNG OR TO BE
 NEW.?
  
 3)NOTE: PLEASE SEE BATH RMS ARE SHOWN W/
 NEW GFI'S. THESE NEED TO NOTED FOR
 #12,20A. 210.11C3
  
 4)NOTE: PLEASE SEE DUE TO WORK AS
 DESCRIBED ON APPLICATION, IT APPEARS
 HOUSE MAY BE GETTTING RE-WIRED? IF SO
 PLEASE SHOW MIN ELECTRICAL PER 2002 NEC
 PLEASE INDICATE NEW OR EXISTING PANEL
 AND SIZE.?
 215.5
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]