| 2006-06-14 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04121374 |
| | ADD: 2216 PALM BEACH LAKES BLVD |
| | CONT: ODUM CONSTRUCTION |
| | TEL: (561)997-6698 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW- REVISION |
| | ACTION: DENIED |
| | |
| | REVISION TO INCREASE THE WINDOW SIZES |
| | FROM (14) 3'-0"X4'-0" TO (14) |
| | 3'-0"X5'-0" WINDOWS DENIED. SEE REVISION |
| | |
| | FILED MAY 31,2006, 2 MONTHS AFTER THE |
| | DENIEL FROM THE CONSTRUCTION BOARD OF |
| | AJUSTMENT & APPEAL. THE OWNER FILED FOR |
| | A VARIANCE FOR THE MARCH MARCH 16, 2006 |
| | BOARD MEETING, OUTCOME DENIED FOR THE |
| | ENLARGEMENT OF EAST WINDOWS, CASE# 1293. |
| | |
| | MARCH 17,2005, BOARD OF ADJUSTMENT AND |
| | APPEAL CASE# 1272 IN THE DOCUMENT THE |
| | APPLICANT PROPOSES THE FOLLOWING |
| | VARIANCE. CODE SECTION 705.1.1.2CODE |
| | REQUIRES OPENINGS WITHIN 15 FT OF THE |
| | PROPERTY LINE TO OPENING PROTECTIVES. |
| | REQUEST FIRE SPRINKLERS INSIDE AND OUT |
| | IN LEU OF FIRE RATED GLASS. THERE IS NO |
| | MENTION OF BEING OVER THE ALLOWED 10% |
| | OPENINGS. THE CASE IS GRANTED FOR THE |
| | USE OF A FIRE CURTAIN INSIDE AND OUT |
| | INSTEAD OF FIRE RATED GLASS. |
| | |
| | |
| | 1/06/06 THIRD REVIEW |
| | FOURTH COMMENT: |
| | 4) PLANS A-12 INDICATE THAT THE WINDOWS |
| | ON THE EAST SIDE HAVE INCREASED.WHEN THE |
| | APPLICANT WENT TO THE BOARD OF |
| | ADJUSTMENT AND APPEAL FOR TABLE 600 AS |
| | WELL AS OPENING PROTECTIVES (705.1.1.2) |
| | THE DESIGN WAS 23% OVER THE ALLOWABLE |
| | OPENING SIZE FOR 5'-10' FROM THE |
| | PROPERTY LINE. WITH THE INCREASE IN |
| | OPENING SIZE THE OVERAGE HAS INCREASED |
| | TO 50% OVER THE ALLOWABLE SIZE AND A 27% |
| | ALLOWABLE OPENINGS APPROVED BY THE |
| | BOARD. |
| | |
| | 1/21/05 FIRST REVIEW |
| | SIXTH COMMENT: |
| | 6) DEMO PLAN INDICATES EITHER NEW OR |
| | ENLARGED OPENINGS ON THE EAST SIDE OF |
| | THE BUILDING: |
| | |
| | 6A) SITE PLAN INDICATES THE EAST SIDE OF |
| | THE BUILDING IS APPROXIMATELY 5'-0" |
| | AWAY FROM THE PROPERTY LINE. 705.1.1.2. |
| | REQUIRES AT ALL OPENINGS WITHIN 15' OF |
| | THE PROPERTY LINE SHALL BE EQUIPPED WITH |
| | APPROVED OPENING PROTECTIVES. |
| | |
| | 6B) THE EAST WALL OF THE BUILDING SHALL |
| | HAVE NO MORE THAN 10% OPENINGS IN THE |
| | WALL , THE PROPOSED OPENINGS ARE AT |
| | APPROXIMATELY 27%. SEE TABLE 600, TYPE |
| | VBUILDING. WALL AREA IS FIGURED FLOOR TO |
| | CEILING THE LENGTH OF THE BUILDING. |
| | |
| | 6C) NOTE FOR FIRE RATED GLASS THERE IS |
| | NO LARGE MISSLE IMPACT TESTED WINDOWS OR |
| | DOORS. STORM SHUTTERS WILL BE REQUIRED |
| | FOR THESE OPENINGS. THE REMAINDER OF THE |
| | BUILDING COULD BE EITHER SHUTTERED OF |
| | LARGE MISSLE IMPACT TESTED GLAZING. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |
| | |