2005-12-21 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
 DENIED
  
 REVIEW COMMENTS DATED SEPT. 23 2005
 (ORIGINAL COMMENTS)
 3. ROOF DRAINAGE REF TO SHT M-3
 NOT IN ROLL PLANS NOR DRAWING INDEX.
 4.5.7. SAYS SEE ARCHITECTURAL.
 NOT ADDRESSED.
 8.DATA SUPPLIED BY PLBG CONTRACTOR,
 DENIED. NOT AS SPECIFIED ON SHT P-1
 11.WATER FEATURE HOSE BIBB.
 REF TO SHT P-4, SHT-4 NOT IN ROLL PLANS
 NOR DRAWING INDEX.
 (NEW COMMENTS)
 1B.PROVIDE INFORMATION AS REQUESTED,
 SEC 104.2.1
 2B MEDICAL GAS SHALL BE NOTED, SEPETATE
 PLANS AND PERMIT TO COMPLY WITH THE
 LATEST EDITIONNFPA 99-C
 3B,4BA,B,C,D,E,F,G ALL REFERE TO A WATER
 HEATER LISTED ON SHT P-4, NOT IN THE
 ROLL PLANS NOR IN THE DRAWING INDEX.
  
 WHEN RE- SUBMITTING PLANS PLEASE SUBMITT
 A TRANSMITTAL LETTER FOR ALL DISCIPLINES
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE. IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  