| 2005-12-21 00:00:00 | PAUL SCHMITZ |
| | FBC2001 FUEL GAS CODEPLAN REVIEW |
| | FBC 2001 PLUMBING CODEPLAN REVIEW |
| | FBC 2001 FL ACESSIBILITY CODE PLAN |
| | REVIEW |
| | DENIED |
| | |
| | REVIEW COMMENTS DATED SEPT. 23 2005 |
| | (ORIGINAL COMMENTS) |
| | 3. ROOF DRAINAGE REF TO SHT M-3 |
| | NOT IN ROLL PLANS NOR DRAWING INDEX. |
| | 4.5.7. SAYS SEE ARCHITECTURAL. |
| | NOT ADDRESSED. |
| | 8.DATA SUPPLIED BY PLBG CONTRACTOR, |
| | DENIED. NOT AS SPECIFIED ON SHT P-1 |
| | 11.WATER FEATURE HOSE BIBB. |
| | REF TO SHT P-4, SHT-4 NOT IN ROLL PLANS |
| | NOR DRAWING INDEX. |
| | (NEW COMMENTS) |
| | 1B.PROVIDE INFORMATION AS REQUESTED, |
| | SEC 104.2.1 |
| | 2B MEDICAL GAS SHALL BE NOTED, SEPETATE |
| | PLANS AND PERMIT TO COMPLY WITH THE |
| | LATEST EDITIONNFPA 99-C |
| | 3B,4BA,B,C,D,E,F,G ALL REFERE TO A WATER |
| | HEATER LISTED ON SHT P-4, NOT IN THE |
| | ROLL PLANS NOR IN THE DRAWING INDEX. |
| | |
| | WHEN RE- SUBMITTING PLANS PLEASE SUBMITT |
| | A TRANSMITTAL LETTER FOR ALL DISCIPLINES |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE. IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS, QUESTIONS 561-805-6692 |
| | |