| 2005-12-09 00:00:00 | ** UNSAT ** |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW WHICH STILL NEED TO BE ADDRESSED. |
| | |
| | |
| | 1)NOTE: NOTE #1 NO. |
| | PLEASE SUBMIT MANUFACTURES CUT/SPEC |
| | SHEETS WHICH WILL CORRELATE WITH PLANS |
| | DRAWING SUBMITTED. |
| | PLEASE SEE GENERATOR SPECS SUBMITTED DO |
| | NOT INDICATE A 75KW GEN, PLEASE SEE THE |
| | ONLY REFERENCE TO ANY 75KW GEN, |
| | INDICATES AMPERAGE RATING AT 142A'S, |
| | WHEN DERATED LOAD IS 189A'S? |
| | PLEASE ALSO BEAR IN MIND, THE RATING OF |
| | A NATURAL GAS GENERATOR IS TYPICALLY |
| | LESS THAN THE KW LISTED FOR LP. |
| | PLEASE ALSO SEE NO SPECS/SHEETS FOR ATS |
| | COULD BE LOCATED ON PACKAGES. |
| | |
| | |
| | 2)NOTE: NOTE #2 OK. |
| | |
| | 3)NOTE: NOTE #3 NO, |
| | PLEASE SUBMIT THE SIGNED, DATED AND |
| | SEALED WIND LOADING CALCULATIONS AS |
| | REQUESTED. |
| | IT WAS NOTED THAT THERE IS A LIGHTING |
| | SUBMITTIAL PACKAGE, HOWEVER THIS ONLY |
| | REFERENCES TO FIXTURES,POLES ETC WITH |
| | OUT PROVIDING INFORMATION NEEDED. |
| | PLEASE KNOW, IF SITE LIGHTING PLAN MAY |
| | BE DELETED FROM PACKAGE, HOWEVER,A |
| | SEPARATE PERMIT APPLICATION, PLANS, FEES |
| | ETC WILL BE REQUIRES BEFORE ANY SITE |
| | LIGHTING MAY START. |
| | NOTE WAS ADDED TO ESP SHEETS WITH |
| | REFERENCE TO FBC 140. |
| | |
| | 4)NOTE: NOTE #4 OK. |
| | |
| | 5)NOTE: NOTE #5 NO, PLEASE SEE ALL SETS |
| | ARE STILL SUBMITTED AS INDIVIDUAL SHEETS |
| | AND SETS ARE NOT PLACED AND ATTACHED |
| | TOGETHER. |
| | |
| | 6)NOTE: NOTE #6 OK, HOWEVER PLEASE SEE |
| | NOTE #1, AS RATING OF GEN IS STILL TO BE |
| | VERIFIED. |
| | |
| | 7)NOTE: NOTE #7 OK. |
| | |
| | 8)NOTE: NOTE #8 OK. |
| | |
| | 9)NOTE: NOTE #9 OK. |
| | |
| | 10)NOTE: NOTE #10 OK. |
| | |
| | 11)NOTE: NOTE #11 OK. |
| | |
| | 12)NOTE: NOTE #12 NO, TO BE VERIFIED, |
| | SEE NOTE #1. |
| | |
| | 13)NOTE: NOTE #13 OK. |
| | |
| | 14)NOTE: NOTE #14 OK. |
| | |
| | 15)NOTE: NOTE #15 OK. |
| | |
| | PLEASE BE SURE TO SUBMIT THE ABOVE |
| | INFORMATION FOR REVIEW. |