Plan Review Notes
Plan Review Notes For Permit 04121374
Permit Number 04121374
Review Stop P
Sequence Number 2
Notes
Date Text
2005-09-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 NFPA 99C GAS & VACUUM SYSTEMS
  
 A. FROM PREVIOUS REVIEW: COMMENT NUMBERS
 TO STAY THE SAME AS FIRST REVIEW:
 3) SHT A-9 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106, AND 1107 AND ALL
 SUBSECTIONS. SHOW TOTAL SQUARE FOOTAGE
 FOR ROOF, AND SHOW 1/2 AREA OF ALL
 VERTICAL WALLS, INCLUDING PARAPETS ADDED
 TO SQUARE FOOTAGE. ALSO IN CALCULATION,
 SHOW THE AREA OF ANY ROOF DRAINING ONTO
 THE ROOF FROM ABOVE. SHOW THE LOCATION
 OF ALL PRIMARY AND SECONDARY ROOF
 DRAINS. SECTION 104.2.1. - COMMENT
 RESPONSE NOTED ON SHT A-9 NOTE #3.
 ALTHOUGH NO NEW ROOF AREA IS ADDED, NEW
 VERTICAL AREAS FROM THE MANSARD ROOF ON
 THREE SIDES OF ROOF AND THE VERTICAL
 WALLS OF THE CUPOLA WILL ADD TO THE
 SQUARE FOOTAGE PER SECTION 1106.4. ALSO
 AS INDICATED IN NOTE #3 THE ROOF HAS NO
 ROOF DRAINS, BUT THE GUTTER AND
 DOWNSPOUTS SHALL BE SIZED PER SF OF THE
 ROOF, TABLE 1106.6 AND DOWNSPOUTS PER
 TABLE 1106.2.
 4) SHTS A-16 & A-17 LOUNGE SINKS SHALL
 COMPLY WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. (FORWARD APPROACH CLEAR
 FLOOR SPACE REQUIRED). SUBMIT DETAILS. -
 RESPONSE NOTED, BUT THE FOLLOWING
 INFORMATION IS REQUIRED:
 DETAILS #9 & 10 SHT A-16 & #11 A-17
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH - SINK MODEL
 INDICATED IS 7-11/16", AND MAX DEPTH IS
 6-1/2"
 D. 11-4.24.5 CLEAR FLOOR SPACE -
 FORWARD APPROACH IS REQUIRED AND SHALL
 EXTEND A MAXIMUM 19" UNDERNEATH THE SINK
 - CABINET DOORS ARE NOT ALLOWED IN THE
 CLEAR FLOOR SPACE.
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 (N1) GARBAGE DISPOSAL CAN NOT BE IN THE
 CLEAR FLOOR SPACE FOR THE SINK.
 SHT A-5 INDICATES A SINK IN THE OWNERS
 LOUNGE, BUT DETAIL #9 SHT A-16 DOES NOT
 SHOW THE SINK. PLEASE CLARIFY. SECTION
 104.2.1.
 5) SHT A-24 DETAILS 1, 2, 3, & 4 THE
 WATER CLOSETS SHALL BE 18" FROM
 CENTERLINE OF THE FIXTURE TO THE WALL.
 SEE FIG 28. THE LAV SHALL BE MINIMUM 15"
 FROM THE CENTERLINE OF THE FIXTURE TO
 THE WALL. (CENTERED ON CLEAR FLOOR SPACE
 30" MEASUREMENT). - DETAIL #4
 INFORMATION REQUIRED NOT SHOWN.
 7) SHT A-24 DETAIL 5, PRIVATE RESTROOM
 TO BE ADAPTABLE. SECTION 11-4.1.3(11).
 SUBMIT DETAILS SHOWING BACKING FOR GRAB
 BARS AT W/C & SHOWER. SHOW W/C AT 18" TO
 CENTERLINE OFF WALL, LAV TO BE MINIMUM
 15" TO CENTERLINE OFF WALL, SHOWER SHALL
 SHOW BACKING FOR SEAT (IF REQUIRED -
 INDICATE SIZE OF SHOWER), SHOW LOCATION
 OF CONTROLS, AND SHOW CURB SIZE, (MAX.
 1/2") IF PROVIDED. ALSO SHOW 5' TURNING
 AREA. SEE SECTIONS 11-4.16, 11-4.19,
 11-4.21. 11-4.22. - PER SECTION
 11-4.21.2 THE SIZE OF THE SHOWER STALL
 SHALL COMPLY WITH FIGURE 35(A) OF 35(B).
 THE SIZE OF THE SHOWER STALL SHOWN DOES
 NOT COMPLY WITH EITHER. - NO CURB HEIGHT
 IS SHOWN.
 ***NOTE ALL PLUMBING SHEETS HAVE BEEN
 RENUMBERED****
 8) SHT P0.1 PLUMBING FIXTURE SCHEDULE,
 SUBMIT MANUF SPECIFICATION SHEETS FOR
 THE TANKLESS WATER HEATERS. LISTING IS
 REQUIRED. SECTION 303.4. - NOW ON SHEET
 P-4, NO MANUF. SHEETS SUBMITTED.
 11) SHT P1.2 WATERFALL, INDICATE METHOD
 OF BACKFLOW PREVENTION REQUIRED ON THE
 WATER SUPPLY OF THE WATERFALL. SECTION
 608. KEYED NOTES #2. - NO RESPONSE
 NOTED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION. -
 NO RESPONSE TO THIS REQUEST.
  
 ***************NEW COMMENTS*************
 1B. SHT P-1 SUBMIT MANUF. SPECIFICATION
 SHEETS FOR THE SCAVANGER SYSTEM. PLEASE
 SUBMIT MORE INFORMATION ON THE SYSTEM,
 AS IN THE INSTALLATION INSTRUCTIONS.
 SECTION 104.2.1.
 2B. SHT P-2 PLEASE INDICATE THE NUMBER
 OF OXYGEN TANKS AND THE AMOUNT OF OXYGEN
 TO BE STORED IN THE CLOSET. - IF MORE
 THAN ONE TANK TO BE USED ON THE MANIFOLD
 THAN AN AUTOMATIC SWITCH OVER WITH
 EXPLOSION PROOF VALVES ARE REQUIRED. - A
 VENT TO THE OUTSIDE IS REQUIRED FROM THE
 REGULATOR AND SHALL BE OF COPPER
 MATERIAL. - THE CLOSET SHALL BE VENTED.
 - A MASTER ALARM IS REQUIRED WITH
 PRESSURE INDICATOR AND RESERVE IN USE
 INDICATOR. - SOLID DOOR REQUIRED WITH A
 1 HOUR OR 2 HOUR FIRE RATING. (TO BE
 DETERMINED BY AMOUNT OF OXYGEN).
 CONTRACTOR SHALL APPLY FOR SEPARATE MED
 GAS PERMIT AND SHALL BE CERTIFIED AS A
 CONTRACTOR AND THE INSTALLER SHALL BE
 CERTIFIED WITH PICTURE I.D. AND
 CERTIFICATION AT TIME OF APPLICATION.
 3B. SHT P-2 THE FLOOR DRAIN FOR THE
 WATER HEATER IS NOT APPROVED AS AN
 INDIRECT WASTE RECEPTOR. A FLOOR SINK OR
 A HUB DRAIN WILL BE REQUIRED PER
 SECTIONS 802.3 & 802.3.2.
 4B. SEPARATE GAS PERMIT REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. - NO ALL CUT SECTION
 LENGTHS SHOWN.
 B. TYPE OF GAS, (LP OR NATURAL)
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 F. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 5B. PLANS SHALL BE SUBMITTED AS SETS OF
 PLANS. LOOSE SHEETS NOT APPROVED.
 SECTION 104.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved