| Date |
Text |
| 2005-09-19 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | NFPA 99C GAS & VACUUM SYSTEMS |
| | |
| | A. FROM PREVIOUS REVIEW: COMMENT NUMBERS |
| | TO STAY THE SAME AS FIRST REVIEW: |
| | 3) SHT A-9 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS PER |
| | SECTIONS 1106, AND 1107 AND ALL |
| | SUBSECTIONS. SHOW TOTAL SQUARE FOOTAGE |
| | FOR ROOF, AND SHOW 1/2 AREA OF ALL |
| | VERTICAL WALLS, INCLUDING PARAPETS ADDED |
| | TO SQUARE FOOTAGE. ALSO IN CALCULATION, |
| | SHOW THE AREA OF ANY ROOF DRAINING ONTO |
| | THE ROOF FROM ABOVE. SHOW THE LOCATION |
| | OF ALL PRIMARY AND SECONDARY ROOF |
| | DRAINS. SECTION 104.2.1. - COMMENT |
| | RESPONSE NOTED ON SHT A-9 NOTE #3. |
| | ALTHOUGH NO NEW ROOF AREA IS ADDED, NEW |
| | VERTICAL AREAS FROM THE MANSARD ROOF ON |
| | THREE SIDES OF ROOF AND THE VERTICAL |
| | WALLS OF THE CUPOLA WILL ADD TO THE |
| | SQUARE FOOTAGE PER SECTION 1106.4. ALSO |
| | AS INDICATED IN NOTE #3 THE ROOF HAS NO |
| | ROOF DRAINS, BUT THE GUTTER AND |
| | DOWNSPOUTS SHALL BE SIZED PER SF OF THE |
| | ROOF, TABLE 1106.6 AND DOWNSPOUTS PER |
| | TABLE 1106.2. |
| | 4) SHTS A-16 & A-17 LOUNGE SINKS SHALL |
| | COMPLY WITH SECTION 11-4.24 AND ALL |
| | SUBSECTIONS. (FORWARD APPROACH CLEAR |
| | FLOOR SPACE REQUIRED). SUBMIT DETAILS. - |
| | RESPONSE NOTED, BUT THE FOLLOWING |
| | INFORMATION IS REQUIRED: |
| | DETAILS #9 & 10 SHT A-16 & #11 A-17 |
| | A. 11-4.24.2 HEIGHT |
| | B. 11-4.24.3 KNEE CLEARANCE |
| | C. 11-4.24.4 SINK DEPTH - SINK MODEL |
| | INDICATED IS 7-11/16", AND MAX DEPTH IS |
| | 6-1/2" |
| | D. 11-4.24.5 CLEAR FLOOR SPACE - |
| | FORWARD APPROACH IS REQUIRED AND SHALL |
| | EXTEND A MAXIMUM 19" UNDERNEATH THE SINK |
| | - CABINET DOORS ARE NOT ALLOWED IN THE |
| | CLEAR FLOOR SPACE. |
| | E. 11-4.24.6 EXPOSED PIPES & SURFACES |
| | (N1) GARBAGE DISPOSAL CAN NOT BE IN THE |
| | CLEAR FLOOR SPACE FOR THE SINK. |
| | SHT A-5 INDICATES A SINK IN THE OWNERS |
| | LOUNGE, BUT DETAIL #9 SHT A-16 DOES NOT |
| | SHOW THE SINK. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | 5) SHT A-24 DETAILS 1, 2, 3, & 4 THE |
| | WATER CLOSETS SHALL BE 18" FROM |
| | CENTERLINE OF THE FIXTURE TO THE WALL. |
| | SEE FIG 28. THE LAV SHALL BE MINIMUM 15" |
| | FROM THE CENTERLINE OF THE FIXTURE TO |
| | THE WALL. (CENTERED ON CLEAR FLOOR SPACE |
| | 30" MEASUREMENT). - DETAIL #4 |
| | INFORMATION REQUIRED NOT SHOWN. |
| | 7) SHT A-24 DETAIL 5, PRIVATE RESTROOM |
| | TO BE ADAPTABLE. SECTION 11-4.1.3(11). |
| | SUBMIT DETAILS SHOWING BACKING FOR GRAB |
| | BARS AT W/C & SHOWER. SHOW W/C AT 18" TO |
| | CENTERLINE OFF WALL, LAV TO BE MINIMUM |
| | 15" TO CENTERLINE OFF WALL, SHOWER SHALL |
| | SHOW BACKING FOR SEAT (IF REQUIRED - |
| | INDICATE SIZE OF SHOWER), SHOW LOCATION |
| | OF CONTROLS, AND SHOW CURB SIZE, (MAX. |
| | 1/2") IF PROVIDED. ALSO SHOW 5' TURNING |
| | AREA. SEE SECTIONS 11-4.16, 11-4.19, |
| | 11-4.21. 11-4.22. - PER SECTION |
| | 11-4.21.2 THE SIZE OF THE SHOWER STALL |
| | SHALL COMPLY WITH FIGURE 35(A) OF 35(B). |
| | THE SIZE OF THE SHOWER STALL SHOWN DOES |
| | NOT COMPLY WITH EITHER. - NO CURB HEIGHT |
| | IS SHOWN. |
| | ***NOTE ALL PLUMBING SHEETS HAVE BEEN |
| | RENUMBERED**** |
| | 8) SHT P0.1 PLUMBING FIXTURE SCHEDULE, |
| | SUBMIT MANUF SPECIFICATION SHEETS FOR |
| | THE TANKLESS WATER HEATERS. LISTING IS |
| | REQUIRED. SECTION 303.4. - NOW ON SHEET |
| | P-4, NO MANUF. SHEETS SUBMITTED. |
| | 11) SHT P1.2 WATERFALL, INDICATE METHOD |
| | OF BACKFLOW PREVENTION REQUIRED ON THE |
| | WATER SUPPLY OF THE WATERFALL. SECTION |
| | 608. KEYED NOTES #2. - NO RESPONSE |
| | NOTED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. - |
| | NO RESPONSE TO THIS REQUEST. |
| | |
| | ***************NEW COMMENTS************* |
| | 1B. SHT P-1 SUBMIT MANUF. SPECIFICATION |
| | SHEETS FOR THE SCAVANGER SYSTEM. PLEASE |
| | SUBMIT MORE INFORMATION ON THE SYSTEM, |
| | AS IN THE INSTALLATION INSTRUCTIONS. |
| | SECTION 104.2.1. |
| | 2B. SHT P-2 PLEASE INDICATE THE NUMBER |
| | OF OXYGEN TANKS AND THE AMOUNT OF OXYGEN |
| | TO BE STORED IN THE CLOSET. - IF MORE |
| | THAN ONE TANK TO BE USED ON THE MANIFOLD |
| | THAN AN AUTOMATIC SWITCH OVER WITH |
| | EXPLOSION PROOF VALVES ARE REQUIRED. - A |
| | VENT TO THE OUTSIDE IS REQUIRED FROM THE |
| | REGULATOR AND SHALL BE OF COPPER |
| | MATERIAL. - THE CLOSET SHALL BE VENTED. |
| | - A MASTER ALARM IS REQUIRED WITH |
| | PRESSURE INDICATOR AND RESERVE IN USE |
| | INDICATOR. - SOLID DOOR REQUIRED WITH A |
| | 1 HOUR OR 2 HOUR FIRE RATING. (TO BE |
| | DETERMINED BY AMOUNT OF OXYGEN). |
| | CONTRACTOR SHALL APPLY FOR SEPARATE MED |
| | GAS PERMIT AND SHALL BE CERTIFIED AS A |
| | CONTRACTOR AND THE INSTALLER SHALL BE |
| | CERTIFIED WITH PICTURE I.D. AND |
| | CERTIFICATION AT TIME OF APPLICATION. |
| | 3B. SHT P-2 THE FLOOR DRAIN FOR THE |
| | WATER HEATER IS NOT APPROVED AS AN |
| | INDIRECT WASTE RECEPTOR. A FLOOR SINK OR |
| | A HUB DRAIN WILL BE REQUIRED PER |
| | SECTIONS 802.3 & 802.3.2. |
| | 4B. SEPARATE GAS PERMIT REQUIRED. THE |
| | FOLLOWING INFORMATION IS REQUIRED: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. - NO ALL CUT SECTION |
| | LENGTHS SHOWN. |
| | B. TYPE OF GAS, (LP OR NATURAL) |
| | C. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | E. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | F. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | 5B. PLANS SHALL BE SUBMITTED AS SETS OF |
| | PLANS. LOOSE SHEETS NOT APPROVED. |
| | SECTION 104.2.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |