Plan Review Notes
Plan Review Notes For Permit 04121374
Permit Number 04121374
Review Stop M
Sequence Number 2
Notes
Date Text
2005-09-22 00:00:00DENIED:
 1.PLAN SHEET A-11 INDICATES 19'8" TO
 THE TOP OF THE PARAPET.PLEASE INDICATE
 ROOF ACCESS FOR EQUIPMENT MAINTENANCE.
 PER 2001 FBC(M)306.5 EQUIPMENT LOCATED
 ON A ROOF AT A HEIGHT GREATER THAN 16FT,
 A PERMANENT MEANS OF ACCESS WILL BE
 REQUIRED.PLEASE INDICATE ACCESS.
  
 2.PLAN SHEET P-2 INDICATES EMERGENCY
 GENERATOR.PLEASE PROVIDE DISTANCE FROM
 OPENINGS (DOORS, & WINDOWS) 2001
 FBC(M)401.5.2.SITE PLAN DOES NOT
 INDICATE LOCATION OF EMERGENCY
 GENERATOR.PLEASE NOTE PER 2001 FBC(M)
 EQUIPMENT INSTALLED IN LOCATION WHERE
 SUBJECT TO DAMAGE SHALL BE PROTECTED BY
 APPROVED BARRIERS.PLEASE PROVIDE
 SUBMITTAL FOR THE GENERATOR.
  