Plan Review Notes
Plan Review Notes For Permit 04121374
Permit Number 04121374
Review Stop E
Sequence Number 2
Notes
Date Text
2005-09-04 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE SUBMIT MANUFACTURE
 SPEC/CUT SHEETS FOR GENERATOR, AUTOMATIC
 TRANSFER SWITCH, AND ANY SUB-BASE FUEL
 TANK.
 PLEASE BE SURE ALL INDICATE LISTINGS
 FROM A NRTL.
 PLEASE BE SURE DISCONNECTING MEANS IS
 RATED AS "SERVICE EQUIPMENT" 225.36.
  
 2)NOTE: PLEASE SEE BUILDING REVIEW
 COMMENTS PERTAING TO CHAPTER 34 OF THE
 FBC. PLEASE SEE ANY REQUIREMENTS WHICH
 MAY AFFECT ELECTRICLA PLANS.
  
 3)NOTE: PLEASE SUBMITWIND LOADING
 CALCULATIONS FOR NEW SITE LIGHTING
 POLES.
 MUST MEET FBC 140 MPH.
  
 4)NOTE: PLEASE SEE THAT ARCHITECTS TITLE
 BLOCK CONTAINS THE "PRINTED NAME AND
 LICENSE NUMBER" FOR THE ARCHITECT. FAC
 61G1-16.004
 PLEASE KNOW, THIS IS REQUIRED ON ALL
 SHEETS AND FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 5)NOTE: PLEASE SUBMIT SETS OF PLANS
 ATTACHED TOGETHER INTO SETS. PLEASE SEE
 PLANS WERE SUBMITTED AS INDIVIDUAL
 SHEETS.
 PLEASE BE SURE ALL OLD/VOIDED SHEETS ARE
 REMOVED AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONE SET OF OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE.
  
 6)NOTE: PLEASE SEE LOADS INDICATED FOR
 RTU'S ON EDP, MUST BE FIGURED AS ALL
 LOADS ON AND UNDER HEAT UNLESS AN
 AUTOMATIC MEANS OF LOAD SHEDDING IS
 PROVIDED.
 IF LOAD SHEDDING WILL BE USED, PLEASE
 PROVIDE A WIRING DETAIL (ETC) FOR
 METHOD, WIRING TO BE USED.
 702.5
  
 7)NOTE: PLEASE SEE LOADS ON OPTIONAL
 BACK -UP POWER. PLEASE SEE GENERAL
 LTS.RECEPTS LOADS ARE PERMITTED TO BE
 DE-RATED, HOWEVER ANY CONNECT MOTOR
 LOADS, APPLIANCE LOADS, MUST BE FIGURED
 AT 100%.
  
 8)NOTE: PLEASE SEE 210.8B3 IN KITCHENS
 OTHER THAN IN DWELLING UNITS WHICH
 REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT
 RECEPTACLES IN NONDWELLING-TYPE KITCHENS
 TO BE GFCI PROTECTED. THIS REQUIREMENT
 APPLIES TO EACH AND EVERY 15- AND
 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE,
 WHETHER OR NOT THE RECEPTACLE SERVES
 COUNTERTOP APPLIANCES.
  
 9)NOTE: PLEASE SEE THAT PLANS SHOULD
 ALSO INDICATE SIGNAGE REQUIRED AT
 DISCONNECTING MEANS AT ELECTRICAL ROOM
 FOR GENERATOR FEED.
 PLEASE VERIFY HOW NEW GENERATOR WILL GET
 TO EXISTING ELECTRICAL RM?
 PLEASE SEE A DISCONNECTING MEANS AT BLDG
 MAY ALSO BE REQUIRED IF FED OVERHEAD
 INTO BLDG.. IF GEN IS FED FROM OUTSIDE
 BLDG (AROUND) OR UNDER GROUND, THIS DISC
 AT ELECTRICAL ROOM WILL BE OK.
 225.31,225.34,110.27
  
 10)NOTE: PLEASE SEE NOTES ON ELECTRICAL
 RISER DIAGRAM PAGE WHICH NOTES PANEL
 "MPD", THIS SEEMS TO BE A MISPRINT?
 PLEASE CORRECT.
  
 11)NOTE: PLEASE SEE FIRE REVIEW NOTES:
 PLEASE SEE A "KNOX BOX" MAY BE REQUIRED
 AND LOCATION DETERMINED BY FIRE MARSHALS
 OFFICE.
 PLEASE SEE FIRE ALARM CONTROL PANEL AND
 GENERATOR ANNUNCIATOR PANEL SHALL BE
 GROUPED. THIS LOCATION WILL ALSO BE
 NOTED BY TH FMO.
 PLEASE SHOW GAP ON PLANS.
  
 12)NOTE: PLEASE VERIFY OCP AT GENERATOR,
 AS 70KW 3/0 120/208V DOES NOT SEEM TO
 PROVIDE 250A'S???
 215.5
  
 13)NOTE: PLEASE CORRELATE ELECTRICAL RM
 LAYOUT WITH ELECTRICAL POWER PLANS FOR
 LOCATIONS OF EQUIPMENT.
 215.5
  
 14)NOTE: PLEASE CORRELATE WATER HEATERS
 AND LOADS SHOWN.
 PLEASE SEE LOAD CALCS SHOWS 24KW, YET
 PANEL "C" ALSO SHOWS AN 11KW WH?
 PLEASE ALSO SEE CIRCUITING SHOWS PUMP
 AND WH?
 PLEASE SEE 422.11F FOR UNITS OVER 48A'S.
 SHOWS A SINGLE OCP FOR UNIT??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  