Plan Review Notes
Plan Review Notes For Permit 04121374
Permit Number 04121374
Review Stop P
Sequence Number 1
Notes
Date Text
2005-01-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) IRRIGATION PLANS AND PERMIT ARE
 REQUIRED. SECTION 104.3.1.1.
 2) SHT A-3 IN THE INSTALLATION OR
 REMOVAL OF ANY PART OF A DRAINATE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 SECTION 704.5.
 3) SHT A-9 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106, AND 1107 AND ALL
 SUBSECTIONS. SHOW TOTAL SQUARE FOOTAGE
 FOR ROOF, AND SHOW 1/2 AREA OF ALL
 VERTICAL WALLS, INCLUDING PARAPETS ADDED
 TO SQUARE FOOTAGE. ALSO IN CALCULATION,
 SHOW THE AREA OF ANY ROOF DRAINING ONTO
 THE ROOF FROM ABOVE. SHOW THE LOCATION
 OF ALL PRIMARY AND SECONDARY ROOF
 DRAINS. SECTION 104.2.1.
 4) SHTS A-16 & A-17 LOUNGE SINKS SHALL
 COMPLY WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. (FORWARD APPROACH CLEAR
 FLOOR SPACE REQUIRED). SUBMIT DETAILS.
 5) SHT A-24 DETAILS 1, 2, 3, & 4 THE
 WATER CLOSETS SHALL BE 18" FROM
 CENTERLINE OF THE FIXTURE TO THE WALL.
 SEE FIG 28. THE LAV SHALL BE MINIMUM 15"
 FROM THE CENTERLINE OF THE FIXTURE TO
 THE WALL. (CENTERED ON CLEAR FLOOR SPACE
 30" MEASUREMENT).
 6) SHT A-24 DETAIL 4, TOILET ROOM 129
 SHALL BE ACCESSIBLE. "IF TOILET ROOMS
 ARE PROVEDED. THEN EACH PUBLIC AND
 COMMON USE TOILET ROOM SHALL COMPLY WITH
 SECTION 11-4.22. SECTIONS 11-4.1.2(6) &
 11-4.1.3(11). SUBMIT DETAILS.
 7) SHT A-24 DETAIL 5, PRIVATE RESTROOM
 TO BE ADAPTABLE. SECTION 11-4.1.3(11).
 SUBMIT DETAILS SHOWING BACKING FOR GRAB
 BARS AT W/C & SHOWER. SHOW W/C AT 18" TO
 CENTERLINE OFF WALL, LAV TO BE MINIMUM
 15" TO CENTERLINE OFF WALL, SHOWER SHALL
 SHOW BACKING FOR SEAT (IF REQUIRED -
 INDICATE SIZE OF SHOWER), SHOW LOCATION
 OF CONTROLS, AND SHOW CURB SIZE, (MAX.
 1/2") IF PROVIDED. ALSO SHOW 5' TURNING
 AREA. SEE SECTIONS 11-4.16, 11-4.19,
 11-4.21. 11-4.22.
 8) SHT P0.1 PLUMBING FIXTURE SCHEDULE,
 SUBMIT MANUF SPECIFICATION SHEETS FOR
 THE TANKLESS WATER HEATERS. LISTING IS
 REQUIRED. SECTION 303.4.
 9) SHT P1.1 DEMO NOTES. NO DEAD ENDS ON
 THE SANT. SYSTEM. SECTION 704.5
 10) SHTS P1.1 & P5.1 ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
 SECTION 909.1 (SEE ALL BATHROOM GROUPS -
 AND REDLINE EXAMPLES ON ONE SET OF SANT.
 RISERS). SECTION 909.1
 11) SHT P1.2 WATERFALL, INDICATE METHOD
 OF BACKFLOW PREVENTION REQUIRED ON THE
 WATER SUPPLY OF THE WATERFALL. SECTION
 608. KEYED NOTES #2.
 12) SHT P1.2 KEYED NOTES #1 BACKFLOW
 PREVENTER SHALL BE INSTALLED MINIMUM OF
 12" ABOVE GRADE TO BOTTOM OF OUTLET.
 13) SHT P5.1 SANT. RISER DIAGRAM, DOUBLE
 SANITARY TEE PATTERNS SHALL NOT RECEIVE
 THE DISCHARGE OF FIXTURES OR APPLIANCES
 WITH PUMPING ACTION DISCHARGE. SECTION
 706.3. (SEE WASHERS ROOM 149).
 14) SHT P5.2 WATER HAMMER ARRESTORS ARE
 REQUIRED AT THE WASHERS. SECTION 604.9.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  