| 2005-01-24 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) IRRIGATION PLANS AND PERMIT ARE |
| | REQUIRED. SECTION 104.3.1.1. |
| | 2) SHT A-3 IN THE INSTALLATION OR |
| | REMOVAL OF ANY PART OF A DRAINATE |
| | SYSTEM, DEAD ENDS SHALL BE PROHIBITED. |
| | SECTION 704.5. |
| | 3) SHT A-9 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS PER |
| | SECTIONS 1106, AND 1107 AND ALL |
| | SUBSECTIONS. SHOW TOTAL SQUARE FOOTAGE |
| | FOR ROOF, AND SHOW 1/2 AREA OF ALL |
| | VERTICAL WALLS, INCLUDING PARAPETS ADDED |
| | TO SQUARE FOOTAGE. ALSO IN CALCULATION, |
| | SHOW THE AREA OF ANY ROOF DRAINING ONTO |
| | THE ROOF FROM ABOVE. SHOW THE LOCATION |
| | OF ALL PRIMARY AND SECONDARY ROOF |
| | DRAINS. SECTION 104.2.1. |
| | 4) SHTS A-16 & A-17 LOUNGE SINKS SHALL |
| | COMPLY WITH SECTION 11-4.24 AND ALL |
| | SUBSECTIONS. (FORWARD APPROACH CLEAR |
| | FLOOR SPACE REQUIRED). SUBMIT DETAILS. |
| | 5) SHT A-24 DETAILS 1, 2, 3, & 4 THE |
| | WATER CLOSETS SHALL BE 18" FROM |
| | CENTERLINE OF THE FIXTURE TO THE WALL. |
| | SEE FIG 28. THE LAV SHALL BE MINIMUM 15" |
| | FROM THE CENTERLINE OF THE FIXTURE TO |
| | THE WALL. (CENTERED ON CLEAR FLOOR SPACE |
| | 30" MEASUREMENT). |
| | 6) SHT A-24 DETAIL 4, TOILET ROOM 129 |
| | SHALL BE ACCESSIBLE. "IF TOILET ROOMS |
| | ARE PROVEDED. THEN EACH PUBLIC AND |
| | COMMON USE TOILET ROOM SHALL COMPLY WITH |
| | SECTION 11-4.22. SECTIONS 11-4.1.2(6) & |
| | 11-4.1.3(11). SUBMIT DETAILS. |
| | 7) SHT A-24 DETAIL 5, PRIVATE RESTROOM |
| | TO BE ADAPTABLE. SECTION 11-4.1.3(11). |
| | SUBMIT DETAILS SHOWING BACKING FOR GRAB |
| | BARS AT W/C & SHOWER. SHOW W/C AT 18" TO |
| | CENTERLINE OFF WALL, LAV TO BE MINIMUM |
| | 15" TO CENTERLINE OFF WALL, SHOWER SHALL |
| | SHOW BACKING FOR SEAT (IF REQUIRED - |
| | INDICATE SIZE OF SHOWER), SHOW LOCATION |
| | OF CONTROLS, AND SHOW CURB SIZE, (MAX. |
| | 1/2") IF PROVIDED. ALSO SHOW 5' TURNING |
| | AREA. SEE SECTIONS 11-4.16, 11-4.19, |
| | 11-4.21. 11-4.22. |
| | 8) SHT P0.1 PLUMBING FIXTURE SCHEDULE, |
| | SUBMIT MANUF SPECIFICATION SHEETS FOR |
| | THE TANKLESS WATER HEATERS. LISTING IS |
| | REQUIRED. SECTION 303.4. |
| | 9) SHT P1.1 DEMO NOTES. NO DEAD ENDS ON |
| | THE SANT. SYSTEM. SECTION 704.5 |
| | 10) SHTS P1.1 & P5.1 ONLY THE FIXTURES |
| | WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| | TO THE WET-VENTED HORIZONTAL BRANCH |
| | DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| | DISCHARGE DOWNSTREAM OF THE WET VENT. |
| | SECTION 909.1 (SEE ALL BATHROOM GROUPS - |
| | AND REDLINE EXAMPLES ON ONE SET OF SANT. |
| | RISERS). SECTION 909.1 |
| | 11) SHT P1.2 WATERFALL, INDICATE METHOD |
| | OF BACKFLOW PREVENTION REQUIRED ON THE |
| | WATER SUPPLY OF THE WATERFALL. SECTION |
| | 608. KEYED NOTES #2. |
| | 12) SHT P1.2 KEYED NOTES #1 BACKFLOW |
| | PREVENTER SHALL BE INSTALLED MINIMUM OF |
| | 12" ABOVE GRADE TO BOTTOM OF OUTLET. |
| | 13) SHT P5.1 SANT. RISER DIAGRAM, DOUBLE |
| | SANITARY TEE PATTERNS SHALL NOT RECEIVE |
| | THE DISCHARGE OF FIXTURES OR APPLIANCES |
| | WITH PUMPING ACTION DISCHARGE. SECTION |
| | 706.3. (SEE WASHERS ROOM 149). |
| | 14) SHT P5.2 WATER HAMMER ARRESTORS ARE |
| | REQUIRED AT THE WASHERS. SECTION 604.9. |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |