| 2005-01-24 00:00:00 | 1) DEMOLITION, RENOVATION AND |
| | CONSTRUCTION TO COMPLY WITH NFPA 241. |
| | |
| | 2) DEBRIS SHALL BE REMOVED FROM THE SITE |
| | DAILY. |
| | |
| | 3) BUILDING ADDRESS REQUIRED. A MINIMUM |
| | OF AT LEAST 6" HIGH NUMBERS ARE |
| | REQUIRED. |
| | |
| | 4) INTERIOR WALL AND CEILING FINISH |
| | SHALL COMPLY WITH NFPA 101 LIFE SAFETY |
| | CODE 2000 EDITION CHAPTER 38.3.3.2. |
| | INTERIOR WALL AND CEILING FINISH |
| | COMPLYING WITH 10.2.3 SHALL BE CLASS A |
| | OR CLASS B IN EXITS AND IN ENCLOSED |
| | CORRIDORS FURNISHING ACCESS TO EXITS; |
| | AND CLASS A, CLASS B, OR CLASS C IN |
| | OFFICE AREAS. |
| | |
| | 5) ALL EXIT DOORS SHALL COMPLY WITH NFPA |
| | 101 CHAPTER 7.2.1. |
| | |
| | 6) THE FIRE ALARM SYSTEM SHALL BE CLASS |
| | "A" OR FULLY ADDRESSABLE. |
| | |
| | 7) ALL FIRE ALARM SYSTEMS THAT SUPERVISE |
| | FIRE SPRINKLER SYSTEMS SHALL BE UL |
| | CERTIFICATED AND HAVE DOCUMENTS |
| | ATTESTING TO THIS CERTIFICATION PRIOR TO |
| | FINAL APPROVAL OF THE FIRE ALARM |
| | SYSTEM. |
| | |
| | 8) PLEASE PROVIDE CUT SHEETS FOR CANVAS |
| | AWING SHOWING PROOF FIRE RESISTANT |
| | TREATED. |
| | |
| | 9) SEPARATE SHOP DRAWINGS AND PERMITS |
| | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE |
| | ALARM SYSTEMS REMODEL. |
| | |
| | |