| Date |
Text |
| 2005-01-10 00:00:00 | *********** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE CORRELATE ITEMS SHOWN ON |
| | PLANS WITH PANEL SCHEDULE. |
| | PLEASE SEE PLANS INDICATE A 30KW WATER |
| | HEATER, YET THIS COULD NOT BE LOCATED? |
| | PLEASE SEE 422 FOR MANY ITEMS REQUIRED |
| | FOR LARGE WATER HEATER UNITS OVER 48A'S. |
| | MIN OCP 125%, MAX 150%. |
| | |
| | 2)NOTE: PLEASE VERIFY REQUIRED SIGN |
| | CIRCUIT PER 600.5EACH COMMERCIAL |
| | BUILDING AND EACH COMMERCIAL OCCUPANCY |
| | ACCESSIBLE TO PEDESTRIANS SHALL BE |
| | PROVIDED WITH AT LEAST ONE OUTLET IN AN |
| | ACCESSIBLE LOCATION AT EACH ENTRANCE TO |
| | EACH TENANT SPACE FOR SIGN OR OUTLINE |
| | LIGHTING SYSTEM USE. THE OUTLET(S) SHALL |
| | BE SUPPLIED BY A BRANCH CIRCUIT RATED AT |
| | LEAST 20 AMPERES THAT SUPPLIES NO OTHER |
| | LOAD. |
| | |
| | 3)NOTE: PLEASE SEE ONE OF THE ELECTRICAL |
| | RMS SHOWN ON PLANS FOR ATS MENTIONS |
| | "CLOSET". PLEASE SEE 110.26, 408.7, |
| | 240.24 FOR PANELS NOT PERMITTED ON |
| | CLOSETS/ STORAGE AREAS. ETC. |
| | |
| | 4)NOTE: PLEASE SEE225.31,.32,.36 FOR |
| | MISSING MEANS OF DISC FOR FEEDER FROM |
| | GENERATOR. |
| | PLEASE ALSO SEE GROUPING OF |
| | MAINS.230.72 |
| | |
| | 5)NOTE: PLEASE SUBMIT MALL MANUFACTURE |
| | SPECS FOR GEN/ ATS/ FUEL TANKS ETC |
| | PLEASE BE SURE A LISTING FROM A NRTL IS |
| | SHOWN. |
| | PLEASE SEE 700.8, 702.8 FOR NOTE TO |
| | PLACED ON PLANS. |
| | A SIGN SHALL BE PLACED AT THE SERVICE |
| | ENTRANCE EQUIPMENT INDICATING TYPE AND |
| | LOCATION OF ON-SITE EMERGENCY POWER |
| | SOURCES. |
| | |
| | 6)NOTE: PLEASE CORRELATE RTU'S ON PLANS |
| | AND PANEL SCHEDULES. |
| | KW RATINGS DO NOT SEEM TO CORRELATE. |
| | RTU#1, #2 |
| | |
| | |
| | 7 )NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | |
| | 8)NOTE: PLEASE SUBMIT WIND-LOADING FOR |
| | NEW POLES/ FIXTURES. |
| | MUST BE AT THIS TIME AND MUST MEET FBC |
| | 140 MPH. |
| | |
| | 9)NOTE: PLEASE PROVIDE NOTE/ INFORMATION |
| | ON TYPE OF ENCLOSURE FOR GEN. |
| | |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD VOIDED SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE ONLY. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |