Plan Review Notes
Plan Review Notes For Permit 04121374
Permit Number 04121374
Review Stop E
Sequence Number 1
Notes
Date Text
2005-01-10 00:00:00*********** UNSAT *****************
  
 1)NOTE: PLEASE CORRELATE ITEMS SHOWN ON
 PLANS WITH PANEL SCHEDULE.
 PLEASE SEE PLANS INDICATE A 30KW WATER
 HEATER, YET THIS COULD NOT BE LOCATED?
 PLEASE SEE 422 FOR MANY ITEMS REQUIRED
 FOR LARGE WATER HEATER UNITS OVER 48A'S.
 MIN OCP 125%, MAX 150%.
  
 2)NOTE: PLEASE VERIFY REQUIRED SIGN
 CIRCUIT PER 600.5EACH COMMERCIAL
 BUILDING AND EACH COMMERCIAL OCCUPANCY
 ACCESSIBLE TO PEDESTRIANS SHALL BE
 PROVIDED WITH AT LEAST ONE OUTLET IN AN
 ACCESSIBLE LOCATION AT EACH ENTRANCE TO
 EACH TENANT SPACE FOR SIGN OR OUTLINE
 LIGHTING SYSTEM USE. THE OUTLET(S) SHALL
 BE SUPPLIED BY A BRANCH CIRCUIT RATED AT
 LEAST 20 AMPERES THAT SUPPLIES NO OTHER
 LOAD.
  
 3)NOTE: PLEASE SEE ONE OF THE ELECTRICAL
 RMS SHOWN ON PLANS FOR ATS MENTIONS
 "CLOSET". PLEASE SEE 110.26, 408.7,
 240.24 FOR PANELS NOT PERMITTED ON
 CLOSETS/ STORAGE AREAS. ETC.
  
 4)NOTE: PLEASE SEE225.31,.32,.36 FOR
 MISSING MEANS OF DISC FOR FEEDER FROM
 GENERATOR.
 PLEASE ALSO SEE GROUPING OF
 MAINS.230.72
  
 5)NOTE: PLEASE SUBMIT MALL MANUFACTURE
 SPECS FOR GEN/ ATS/ FUEL TANKS ETC
 PLEASE BE SURE A LISTING FROM A NRTL IS
 SHOWN.
 PLEASE SEE 700.8, 702.8 FOR NOTE TO
 PLACED ON PLANS.
 A SIGN SHALL BE PLACED AT THE SERVICE
 ENTRANCE EQUIPMENT INDICATING TYPE AND
 LOCATION OF ON-SITE EMERGENCY POWER
 SOURCES.
  
 6)NOTE: PLEASE CORRELATE RTU'S ON PLANS
 AND PANEL SCHEDULES.
 KW RATINGS DO NOT SEEM TO CORRELATE.
 RTU#1, #2
  
  
 7 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 8)NOTE: PLEASE SUBMIT WIND-LOADING FOR
 NEW POLES/ FIXTURES.
 MUST BE AT THIS TIME AND MUST MEET FBC
 140 MPH.
  
 9)NOTE: PLEASE PROVIDE NOTE/ INFORMATION
 ON TYPE OF ENCLOSURE FOR GEN.
  
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]