| 2005-01-21 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04121374 |
| | ADD: 2216 PALM BEACH LAKES BLVD |
| | CONT: K & M COMMERCIAL |
| | TEL: (561)383-2817 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) SEE SHEET A-7 DOOR 152A MISSING THE |
| | REQUIRED 18" ON PULL SIDE.11-4.13.6 |
| | MANEUVERING CLEARENCES AT DOORS. MINIMUM |
| | MANEUVERING CLEARENCES AT DOORS THAT ARE |
| | NOT AUTOMATIC OR POWER-ASSISTED SHALL BE |
| | AS SHOWN IN FIG. 25. THE FLOOR OR GROUND |
| | AREA WITH IN THE REQUIRED CLEARENCES |
| | SHALL BE CLEAR & LEVEL. |
| | |
| | 3) ELECTRIC PLAN INDICATES A GENERATOR |
| | AND FUEL TANK BUT NO INDICATION IS ON |
| | THE SITE PLAN? |
| | |
| | 4) DISCEPANCY STRUCTURAL PLANS INDICATE |
| | A DRIVE THROUGH BUT A-6 DOESN'T INDICATE |
| | |
| | ANY FOOTERS, COLUMNS ETC |
| | |
| | 5) THE PLANS SUBMITTED SHALL BE |
| | REVIEWED |
| | AS A NEW BUILDING. CHAPTER 3401.7.2.6 |
| | WHEN OVER 50% OF THE EXISTING BUILDING |
| | ARE MADE DURING ANY 12 MONTH PERIOD, THE |
| | BUILDING SHALL BE MADE TO CONFORM TO THE |
| | |
| | REQUIREMENTS FOR A NEW BUILDING OR BE |
| | ENTIRELY DEMOLISHED. |
| | |
| | 6) DEMO PLAN INDICATES EITHER NEW OR |
| | ENLARGED OPENINGS ON THE EAST SIDE OF |
| | THE BUILDING: |
| | 6A) SITE PLAN INDICATES THE EAST SIDE OF |
| | THE BUILDING IS APPROXIMATELY 5'-0" |
| | AWAY FROM THE PROPERTY LINE. 705.1.1.2. |
| | REQUIRES AT ALL OPENINGS WITHIN 15' OF |
| | THE PROPERTY LINE SHALL BE EQUIPPED WITH |
| | |
| | APPROVED OPENING PROTECTIVES. |
| | 6B) THE EAST WALL OF THE BUILDING SHALL |
| | |
| | HAVE NO MORE THAN 10% OPENINGS IN THE |
| | WALL , THE PROPOSED OPENINGS ARE AT |
| | APPROXIMATELY 27%. SEE TABLE 600, TYPE |
| | V |
| | BUILDING. WALL AREA IS FIGURED FLOOR TO |
| | CEILING THE LENGTH OF THE BUILDING. |
| | 6C) NOTE FOR FIRE RATED GLASS THERE IS |
| | NO LARGE MISSLE IMPACT TESTED WINDOWS OR |
| | |
| | DOORS. STORM SHUTTERS WILL BE REQUIRED |
| | FOR THESE OPENINGS. THE REMAINDER OF THE |
| | BUILDING COULD BE EITHER SHUTTERED OF |
| | LARGE MISSLE IMPACT TESTED GLAZING. |
| | |
| | 7) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 8)FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) WINDOWS FIXED & OPERTABLE |
| | B) MULLIONS |
| | C) EXTERIOR DOORS |
| | D) SKYLIGHTS |
| | E) STRUCTURAL COMPONENTS- TRUSS |
| | ANCHORS |
| | F) ROOFING ASSEMBLIES |
| | |
| | 9) 1707.4.5.1 MULLIONS OCCURRING BETWEEN |
| | INDIVIDUAL WINDOW AND GLASS |
| | DOOR ASSEMBLIES. TESTING REPORTS ARE |
| | REQUIRED BY AN APPROVED TESTING |
| | LABORATORY OR BE ENGINEERED. |
| | |
| | 10) 1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| | ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| | TO THE ROUGH OPENING SUBTRATE. |
| | |
| | 11) 1707.4.3 EACH EXTERIOR DOOR ASSEMBLY |
| | NOT COVERED BY 1707.4.2 |
| | (GLAZED DOORS) SHALL BE LISTED AND TEST- |
| | ED FOR A PERIOD EQUAL TO THE QUANITY |
| | 3600/ V WHERE THE TIME PERIOD IS IN |
| | SECTIONS AND V IS IN MILES PER HR TAKEN |
| | FROM FIGURE 1606. THE TIME PERIOD SHALL |
| | ALSO INCLUDE A 10 SECOND PERIOD AT A |
| | LOAD EQUAL TO 1.5 TIMES THE DESIGN |
| | PRESSURE. DADE COUNTY & SBCCI REPORTS |
| | ARE ACCEPTED. |
| | |
| | 12) PROVIDE POSITIVE & NEGATIVE |
| | PRESSURES FOR ALL OPENINGS, INCLUDE |
| | END ZONES. |
| | |
| | 13) A-21 INDICATES THE USE OF 5/8" CDX |
| | PLYWOOD FOR WALLS OD CUPALO, THIS IS A |
| | TYPE V BUILDING, WALLS TO BE |
| | NONCOMBUSTIBLE., ALSO IN A FIRE DISTRICT |
| | |
| | NO TYPE VI CONSTRUCTION. |
| | |
| | 14) 3106.2 CANOPIES. WHEN LOCATED LESS |
| | THAN 30" FROM AN INTERIOR LOT LINE OR |
| | OTHER STUCTURE, THE CANOPY FRAME AND ITS |
| | SUPPORTS SHALL BE OF NONCOMBUSTILE |
| | MATERIAL, FIRE RESISTANT TREATED |
| | CONSTRUCTION. |
| | |