2005-01-21 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04121374
 ADD: 2216 PALM BEACH LAKES BLVD
 CONT: K & M COMMERCIAL
 TEL: (561)383-2817
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) SEE SHEET A-7 DOOR 152A MISSING THE
 REQUIRED 18" ON PULL SIDE.11-4.13.6
 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARENCES AT DOORS THAT ARE
 NOT AUTOMATIC OR POWER-ASSISTED SHALL BE
 AS SHOWN IN FIG. 25. THE FLOOR OR GROUND
 AREA WITH IN THE REQUIRED CLEARENCES
 SHALL BE CLEAR & LEVEL.
  
 3) ELECTRIC PLAN INDICATES A GENERATOR
 AND FUEL TANK BUT NO INDICATION IS ON
 THE SITE PLAN?
  
 4) DISCEPANCY STRUCTURAL PLANS INDICATE
 A DRIVE THROUGH BUT A-6 DOESN'T INDICATE
  
 ANY FOOTERS, COLUMNS ETC
  
 5) THE PLANS SUBMITTED SHALL BE
 REVIEWED
 AS A NEW BUILDING. CHAPTER 3401.7.2.6
 WHEN OVER 50% OF THE EXISTING BUILDING
 ARE MADE DURING ANY 12 MONTH PERIOD, THE
 BUILDING SHALL BE MADE TO CONFORM TO THE
  
 REQUIREMENTS FOR A NEW BUILDING OR BE
 ENTIRELY DEMOLISHED.
  
 6) DEMO PLAN INDICATES EITHER NEW OR
 ENLARGED OPENINGS ON THE EAST SIDE OF
 THE BUILDING:
 6A) SITE PLAN INDICATES THE EAST SIDE OF
 THE BUILDING IS APPROXIMATELY 5'-0"
 AWAY FROM THE PROPERTY LINE. 705.1.1.2.
 REQUIRES AT ALL OPENINGS WITHIN 15' OF
 THE PROPERTY LINE SHALL BE EQUIPPED WITH
  
 APPROVED OPENING PROTECTIVES.
 6B) THE EAST WALL OF THE BUILDING SHALL
  
 HAVE NO MORE THAN 10% OPENINGS IN THE
 WALL , THE PROPOSED OPENINGS ARE AT
 APPROXIMATELY 27%. SEE TABLE 600, TYPE
 V
 BUILDING. WALL AREA IS FIGURED FLOOR TO
 CEILING THE LENGTH OF THE BUILDING.
 6C) NOTE FOR FIRE RATED GLASS THERE IS
 NO LARGE MISSLE IMPACT TESTED WINDOWS OR
  
 DOORS. STORM SHUTTERS WILL BE REQUIRED
 FOR THESE OPENINGS. THE REMAINDER OF THE
 BUILDING COULD BE EITHER SHUTTERED OF
 LARGE MISSLE IMPACT TESTED GLAZING.
  
 7) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS FIXED & OPERTABLE
 B) MULLIONS
 C) EXTERIOR DOORS
 D) SKYLIGHTS
 E) STRUCTURAL COMPONENTS- TRUSS
 ANCHORS
 F) ROOFING ASSEMBLIES
  
 9) 1707.4.5.1 MULLIONS OCCURRING BETWEEN
 INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 10) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 11) 1707.4.3 EACH EXTERIOR DOOR ASSEMBLY
 NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 12) PROVIDE POSITIVE & NEGATIVE
 PRESSURES FOR ALL OPENINGS, INCLUDE
 END ZONES.
  
 13) A-21 INDICATES THE USE OF 5/8" CDX
 PLYWOOD FOR WALLS OD CUPALO, THIS IS A
 TYPE V BUILDING, WALLS TO BE
 NONCOMBUSTIBLE., ALSO IN A FIRE DISTRICT
  
 NO TYPE VI CONSTRUCTION.
  
 14) 3106.2 CANOPIES. WHEN LOCATED LESS
 THAN 30" FROM AN INTERIOR LOT LINE OR
 OTHER STUCTURE, THE CANOPY FRAME AND ITS
 SUPPORTS SHALL BE OF NONCOMBUSTILE
 MATERIAL, FIRE RESISTANT TREATED
 CONSTRUCTION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026