Plan Review Notes
Plan Review Notes For Permit 04121369
Permit Number 04121369
Review Stop E
Sequence Number 1
Notes
Date Text
2005-01-19 00:00:00********* UNSAT **********
  
 1)NOTE: PLEASE SEE MISSING RECEPT PER
 210.52 W/IN 6' OF DOOR.
  
 2)NOTE: PLEASE SEE PLANS WHICH ARE
 SIGNED,DATED AND SEALED BY AN ENGINEER
 OR ARCH MAY NOT HAVE HAND DRAWN CHANGES
 MADES TO PLANS WITHOUT EACH CHANGED
 BEING SIGNED/DATED BY THE ENGINEER OR
 ARCH. FS 481.221, 471.025
 PLEASE SEE NOTE #1 MAY HAVE BEEN
 REDLINED, HOWEVER DUE TO NOTE #2, THIS
 COULD NOT BE PASSED AND STAMPED AT THIS
 TIME. PLEASE SEE BLDG REVIEW COMMENTS
 FOR THIS.
 PLEASE ALSO SEE ONE SET IS A PHOTOCOPY
 OF SIGNED AND SEALED PLANS WHICH IS NOT
 PERMITTED PER FAC 61G15-23.002, FS
 471.025
 ARCH DEIGNER MAY NOT MAKE THESE
 CHANGES.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO A
 MIN OF TWO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  