| Notes |
| Date |
Text |
| 2005-03-17 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | A) FROM PREVIOUS REVIEW: THE COMMENT | | | NUMBER SHALL STAY THE SAME TO AVOID | | | CONFUSTION. | | | 3) SUBMIT A DETAIL FOR THE KITCHEN AND | | | BREAK ROOM SINKS. SHOW COMPLIANCE WITH | | | SECTION 11-4.24 AND ALL SUBSECTIONS. THE | | | FOLLOWING SUBSECTIONS WERE NOT SHOWN. | | | A) 11-4.24.4 SINK DEPTH | | | B) 11-R.24.5 27" MIN. HEIGHT FOR KNEE | | | CLEARANCE. | | | C) 11-4.24.6 EXPOSED PIPES & SURFACES. | | | D) 11-4.24.7 FAUCETS. | | | 4) SUBMIT A DETAIL FOR THE URINALS | | | SHOWING COMPLIANCE WITH SECTION 11-4.18 | | | AND ALL SUBSECTIONS. NOT SHOWN WAS: | | | A) 11-4.18.4 FLUSH CONTROLS. | | | 5) SUBMIT A DETAIL FOR THE SHOWER | | | SHOWING COMPLIANCE WITH SECTION 11-4.21 | | | AND ALL SUBSECTIONS. NOT SHOWN WAS: | | | A) 11-4.21.5 CONTROLS (HEIGHT NOT | | | SHOWN) | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|