2 |
|
| Notes |
| Date |
Text |
| 2005-03-28 00:00:00 | P-PROVISO | | | | | | 1) PLEASE BE ADVISED THAT ALL WORK MUST | | | COMPLY WITH NFPA 13, 2002 EDITION WHEN | | | SEPARATE SHOP DRAWINGS ARE SUBMITTED. | | | THIS OFFICE ADOPTED THE 2002 EDITION | | | AFTER JAN. 1, 2005. | | | | | | 2) A WRENCH SHALL BE PROVIDED WITH THE | | | SPARE SPRINKLER HEADS. | | | | | | 3) PLEASE BE ADVISED THAT THE FIRE | | | SPRINKLER SYSTEM SHALL BE MONITORED BY A | | | MONITORING COMPANY APPROVED AS A UL | | | LISTED CENTRAL STATION SERVICE. | | | | | | 4) PLEASE BE ADVISED THAT SEPARATE SHOP | | | DRAWINGS AND PERMITS ARE REQUIRED FOR | | | FIRE SPRINKLER AND FIRE ALARM SYSTEMS. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR (561) 835-2910 | | 2005-03-24 00:00:00 | P-PROVISO | | | | | | THANK YOU FOR YOUR EXPLANATIONS | | | RERGARDING THE ORIGINAL REVIEW, HOWEVER | | | ITEM #8 REQUIRES ADDITIONAL | | | CLARIFICATION. | | | | | | 1) PLEASE BE ADVISED THAT SEPARATE SHOP | | | DRAWINGS AND PERMITS ARE REQUIRED FOR | | | BOTH THE FIRE ALARM AND FIRE SPRINKLER | | | SYSTEMS. SHEET E-2 ONLY REFERS TO THE | | | FIRE ALARM SYSTEM. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2910 |
|