Plan Review Notes
Plan Review Notes For Permit 04121254
Permit Number 04121254
Review Stop B
Sequence Number 2
Notes
Date Text
2005-03-21 00:00:00PERMIT: 04121254
 ADD: 1318 MERCER AVE
 CONT: SOUTHERN CONSTRUCTION
 TEL: (561)718-8876
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 1) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT SO THAT FBC TABLE 600
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
 IT MAY REQUIRE REPLATTING, SINCE THE
 SURVEY INDICATES 6 LOTS THAT WOULD
 REQUIRE COMBINING INTO ONE LOT.
  
 2) FBC* 105.3RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA (805-6711),
 DIRECTOR OF THE RESIDENT INSPECTOR
 PROGRAM.A RESIDENT INSPECTOR PROGRAM
 IS REQUIRED, ON THIS PROJECT, DUE TO ONE
 OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION.
  
 3) SINCE THIS BUILDING REQUIRES A
 SPECIAL INSPECTOR, SUBMIT (3) SETS OF
 ALL DOCUMENTS, PLANS, REPORTS, PRODUCT
 APPROVALS, LETTERS AND OR SUBMITTALS .
  
  
 4) THE PLANS SUBMITTED FROM BUTLER
 MANUFACTURING COMPANY SHALL REQUIRE THE
 PLANS TO BE SIGNED WITH ORIGINAL
 SIGNATURE OF THE P.E., ALL 3 SETS NOT
 COPIES OF SIGNATURES.SIGNED & SEALED.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 5) A2.2 ROOF RACK HEIGHT:THE A?C RACK
 DETAIL INDICATES A MINIMUM OF 18" BUT
 DOES NOT PROVIDE INFORMATION IF THE UNIT
 IS 38" WIDE AS PROVIDED BY TABLE 1511.7.
 1511.7 ROOF MOUNTED MECHANICAL UNITS
 SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE MECHANICAL
 EQUIPMENT, APPLIANCES AND SUP PORTS THAT
 ARE EXPOSED TO WIND SHALL BE DESIGNED
 AND INSTALLED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
  
 6) TABLE 600 ISSUES SEE TYPEIV BLDG
 UNPROTECTED, FOOTNOTE (E) UNDER ROOF &
 ROOF CEILING ASSEMBLIES. ONLY FIRE
 RETARDANT TREATED WOOD CAN BE USED FOR
 SHEATHING ON BUILDINGS 2 STORIES OR
 LESS. SEE SHEET S0.2 NOTES PLYWOOD ROOF
 DECKING, ALSO S2.1 SECTION 5&6 PLEASE
 ANNOTE PLANS.
  
 7) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 3 COPIES OF THE
 PRODUCT APPROVAL FOR THRESHOLD OR
 RESIDENT INSPECTOR PROGRAM BUILDING.
  
 8) PROVIDE THE PALM BEACH COUNTY IMPACT
 FEE RECEIPT, PART OF PERMIT PACKAGE
 REQUIREMENTS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026